SIEPC71061753A GA500 Technical Manual
◆
L3: Stall Prevention
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L3-01
(048F)
Stall Prevention during
Accel
Sets the method of the Stall Prevention During Acceleration.
0 : Disabled
1 : Enabled
2 : Intelligent (Ignore Decel Ramp)
3 : Current Limit Acceleration
1
(0 - 3)
L3-02
(0490)
Stall Prevent Level
during Accel
Sets the output current level at which the Stall Prevention function operates during
acceleration where the drive rated output current is 100%.
Note:
The upper limit to the setting range changes when the setting for
C6-01 [Normal /
Heavy Duty Selection]
changes.
•
150% when
C6-01 = 0 [Heavy Duty Rating]
•
120% when
C6-01 = 1 [Normal Duty Rating]
Determined by C6-01
and L8-38
(0 - 150%)
L3-03
(0491)
Stall Prevent Limit
during Accel
Sets the lower limit for the stall prevention level used in the constant output range as a
percentage of the drive rated output current.
50%
(0 - 100%)
L3-04
(0492)
Stall Prevention during
Decel
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
Note:
1.
To connect a dynamic braking option (braking resistor or braking resistor unit)
to the drive, set this parameter to
0 or 3
. Parameter settings
1, 2, 4, 5, and 7
will
enable Stall Prevention function during deceleration, and the dynamic braking
option will not function.
2.
The setting range changes when the
A1-02 [Control Method Selection]
value
changes:
•
When
A1-02 = 5 [OLV/PM]
, the setting range is
0 to 2
.
•
When
A1-02 = 6 or 8 [AOLV/PM or EZOLV]
, the setting range is
0 or 1
.
0 : No
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
3 : General Purpose w/ DB resistor
4 : Overexcitation/High Flux
5 : Overexcitation/High Flux 2
7 : Overexcitation/High Flux 3
1
(Determined by A1-02)
L3-05
(0493)
Stall Prevention during
RUN
Sets the function to enable and disable Stall Prevention During Run.
Note:
•
An output frequency less than 6 Hz disables Stall Prevention during Run. The
setting values of
L3-05
and
L3-06 [Stall Prevent Level during Run]
do not have an
effect.
•
The setting range changes when the
A1-02 [Control Method Selection]
value
changes:
–
A1-02 = 0, 5[V/f, OLV/PM]
: 0 to 2
–
A1-02 =8[EZOLV]
: 0, 3
0 : No
1 : Deceleration Time 1 (C1-02)
2 : Deceleration Time 2 (C1-04)
3 : Intelligent (Ignore Decel Ramp)
Determined by A1-02
(0 - Determined by A1-
02)
L3-06
(0494)
Stall Prevent Level
during Run
Sets the output current level at which the Stall Prevention function is enabled during run
when the drive rated output current is 100%.
Note:
•
This parameter is applicable when
L3-05 = 1, 2 [Stall Prevention during RUN =
Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-04)]
.
•
The upper limit to the setting range changes when the setting for
C6-01 [Normal /
Heavy Duty Selection]
changes.
–
150% when
C6-01 = 0 [Heavy Duty Rating]
–
120% when
C6-01 = 1 [Normal Duty Rating]
Determined by C6-01
and L8-38
(5 - 150%)
L3-11
(04C7)
Overvoltage Suppression
Select
Sets the overvoltage suppression function.
0 : Disabled
1 : Enabled
0
(0, 1)
L3-17
(0462)
DC Bus Regulation
Level
Sets the target value for the DC bus voltage when the overvoltage suppression function
and the Decel Stall Prevention function (Intelligent Stall Prevention) are active.
200 V Class: 375 V, 400
V: 750 V
(200 V Class: 150 to 400
V, 400 V Class: 300 to
800 V)
L3-20
(0465)
Expert
DC Bus Voltage
Adjustment Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...