YASKAWA
SIEPC71061753A GA500 Technical Manual
589
Note:
The
H5-11 [Comm ENTER Command Mode]
setting makes the RAM enter command necessary or not necessary to write parameters
over network communication. When
F6-32 = 0, 1, or 2
, the
H5-11
setting does not have an effect. The RAM enter command is always
necessary to write parameters.
0 : PPO Type
1 : Conventional
2 : PPO (bit0)
This function operates when bit 0 and bit 4 in the register STW have values of 1 (operate). Refer to the
PROFIBUS-DP communication manual for more information.
3 : PPO (Enter)
4 : Conventional (Enter)
5 : PPO (bit0, Enter)
This function operates when bit 0 and bit 4 in the register STW have values of 1 (operate). Refer to the
PROFIBUS-DP communication manual for more information.
■
F6-35: CANopen Node ID Selection
No.
(Hex.)
Name
Description
Default
(Range)
F6-35
(03D0)
CANopen Node ID
Selection
Sets the node address for CANopen communication. Restart the drive after you change the
parameter setting.
0
(0 - 126)
Note:
Be sure to set an address that is different than all other node addresses. Do not set this parameter to
0
. Incorrect parameter settings will
cause
AEr [Station Address Setting Error]
errors and the L.ERR LED on the option will come on.
■
F6-36: CANopen Communication Speed
No.
(Hex.)
Name
Description
Default
(Range)
F6-36
(03D1)
CANopen Communication
Speed
Sets the CANopen communications speed. Restart the drive after you change the parameter
setting.
0
(0 - 8)
0 : Auto-detection
The drive detects the network communication speed and automatically adjusts the communications speed.
1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
■
F6-50: DeviceNet MAC Address
No.
(Hex.)
Name
Description
Default
(Range)
F6-50
(03C1)
DeviceNet MAC Address
Sets the MAC address for DeviceNet communication. Restart the drive after you change the
parameter setting.
0
(0 - 64)
Note:
Be sure to set a MAC address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings
will cause
AEr [Station Address Setting Error]
errors and the MS LED on the option will flash.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...