![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 322](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765322.webp)
322
YASKAWA
SIEPC71061753A GA500 Technical Manual
10.7
Drive Derating
You must derate the drive capacity to operate the drive above the rated temperature, altitude, and default carrier
frequency.
◆
Carrier Frequency Settings and Rated Current Values
The tables in this section show how the drive rated output current changes when the
C6-02 [Carrier Frequency
Selection]
value changes. The output current value changes linearly as the carrier frequency changes. You can use
the values from the tables to calculate a frequency that is not shown.
■
Three-Phase 200 V Class
Table 10.11 Carrier Frequency and Rated Current Derating (Three-Phase 200 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2001
0.8
0.8
0.8
0.8
0.7
0.6
1.2
1.1
1.0
0.9
0.8
0.6
2002
1.6
1.6
1.6
1.6
1.4
1.3
1.9
1.9
1.7
1.6
1.4
1.3
2004
3.0
3.0
3.0
3.0
2.7
2.4
3.5
3.5
3.2
3.0
2.7
2.4
2006
5.0
5.0
5.0
5.0
4.5
4
6.0
6.0
5.4
5.0
4.5
4
2010
8.0
8.0
8.0
7.5
7.0
6.4
9.6
9.1
8.3
7.7
7.1
6.4
2012
11.0
11.0
11.0
10.4
9.6
8.8
12.2
11.9
11.0
10.4
9.6
8.8
2021
17.6
17.6
17.6
16.6
15.3
14.1
21.0
19.8
18.1
17.0
15.5
14.1
2030
25.0
25.0
25.0
23.6
21.8
20
30.0
28.3
25.8
24.2
22.1
20
2042
33.0
33.0
33.0
31.1
28.8
26
42.0
39.4
35.5
32.9
29.7
26
2056
47.0
47.0
47.0
44.3
41.0
38
56.0
52.9
48.3
45.3
41.4
38
2070
60.0
60.0
60.0
56.6
52.3
48
70.0
66.3
60.8
57.2
52.6
48
2082
75.0
75.0
75.0
70.7
65.4
60
82.0
81.4
75.0
70.7
65.4
60
Table 10.12 AOLV/PM Carrier Frequency and Rated Current Derating (Three-Phase 200 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
2001
0.8
0.8
0.8
0.7
0.6
0.5
1.2
1.1
0.9
0.8
0.6
0.5
2002
1.6
1.6
1.6
1.5
1.3
1.1
1.9
1.9
1.7
1.5
1.3
1.1
2004
3.0
3.0
3.0
2.8
2.4
2.0
3.5
3.5
3.1
2.8
2.4
2.0
2006
5.0
5.0
5.0
4.6
4.0
3.4
6.0
5.8
5.2
4.6
4.0
3.4
2010
8.0
8.0
7.8
7.1
6.4
5.7
9.6
8.8
8.0
7.2
6.4
5.6
2012
11.0
11.0
10.7
9.7
8.8
7.9
12.2
11.6
10.7
9.7
8.8
7.9
2021
17.6
17.6
17.1
15.6
14.1
12.6
21.0
19.3
17.5
15.8
14.1
12.4
2030
25.0
25.0
24.3
22.1
20.0
17.9
30.0
27.5
25.0
22.5
20.0
17.5
2042
33.0
33.0
32.1
29.2
26.4
23.6
42.0
38.1
34.2
30.3
26.4
22.5
2056
47.0
47.0
45.7
41.6
37.6
33.6
56.0
51.4
46.8
42.2
37.6
33.0
2070
60.0
60.0
58.3
53.1
48.0
42.9
70.0
64.5
59.0
53.5
48.0
42.5
2082
75.0
75.0
72.9
66.4
60.0
53.6
82.0
79.3
72.9
66.4
60.0
53.6
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...