![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 219](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765219.webp)
6.3 MEMOBUS/Modbus Communications
YASKAWA
SIEPC71061753A GA500 Technical Manual
219
Note:
Set the reserved bit to 0. Do not write the data in the reserved register or the monitor register.
Table 6.11 MEMOBUS/Modbus Communications Command Data
Register No.
(Hex.)
Description
0000
Reserved
0001
Run command, multi-function input command
bit 0
When
H5-12 = 0
, Forward run/stop
1: Forward run, 0: Stop
When
H5-12 = 1
, run/stop
1: Run, 0: Stop
bit 1
When
H5-12 = 0
, Reverse run/stop
1: Reverse run, 0: Stop
When
H5-12 = 1
, Forward/Reverse run
1: Reverse, 0: Forward run
bit 2
External fault
1: EF0 [Option Card External Fault]
bit 3
Fault Reset
1: Reset command
bit 4
Multi-function input 1
When the multi-function input command is
H1-01 = 40 [Forward Run Command (2-Wire Seq)]
, bit 4 is
“
ComRef.
”
Note:
When you switch the bit ON as ComRef, the frequency reference source changes to MEMOBUS/Modbus
communications. When you connect a communication option to the drive, the frequency reference source gives priority to
the communications option.
bit 5
Multi-function input 2
When the multi-function input command is
H1-02 = 41 [Reverse Run Command (2-Wire Seq)]
, bit 5 is
“
ComCtrl.
”
Note:
When you switch the bit ON as ComCtrl, the Run Command source changes to MEMOBUS/Modbus communications.
When you connect a communication option to the drive, the Run Command source gives priority to the communications
option.
bit 6
Multi-function input 3
bit 7
Multi-function input 4
bit 8
Multi-function input 5
bit 9
Multi-function input 6
bit A
Multi-function input 7
bit B - F
Reserved
0002
Frequency Reference
o1-03 [Frequency Display Unit Selection]
(unsigned) sets the units.
0003
Output voltage gain
Units: 0.1%
Setting range: 20 (2.0%) to 2000 (200.0%), the default value at energize: 1000 (100.0%)
0004
Torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Setting for the multi-function analog monitor output terminal AM (10 V/4000 (Hex.))
0008
Reserved
0009
MFDO setting
bit 0
MFDO (terminal MA/MB-MC)
1: ON, 0: OFF
bit 1
Multi-function photocoupler output 1 (terminal P1-C1)
1: ON, 0: OFF
bit 2
Multi-function photocoupler output 2 (terminal P2-C2)
1: ON, 0: OFF
bit 3 - F
Reserved
000A
Pulse train output (Units: 1/1 Hz, setting range: 0 to 32000)
000B - 000E
Reserved
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...