714
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
n3-02: HSB Current Limit Level
No.
(Hex.)
Name
Description
Default
(Range)
n3-02
(0589)
Expert
HSB Current Limit Level
Sets the maximum current output during high-slip braking as a percentage, where
E2-01 [Motor
Rated Current (FLA)]
is 100%. Also set the current suppression to prevent exceeding drive
overload tolerance.
Determined by C6-01 and
L8-38
(0 - 150%)
Note:
The upper limit to the setting range changes when the setting for
C6-01 [Normal / Heavy Duty Selection]
changes.
•
150% when
C6-01 = 0 [Heavy Duty Rating]
•
120% when
C6-01 = 1 [Normal Duty Rating]
When you decrease the setting value for current suppression, it will make the deceleration time longer.
•
When you must detect
ov [DC Bus Overvoltage]
during high-slip braking, set this parameter to a low value.
•
If the motor current increases during high-slip braking, decrease the setting value to prevent burn damage in the
motor.
•
The overload tolerance for the drive is 150% for Heavy Duty Rating (HD) and 110% for Normal Duty Rating
(ND).
■
n3-03: HSB Dwell Time at Stop
No.
(Hex.)
Name
Description
Default
(Range)
n3-03
(058A)
Expert
HSB Dwell Time at Stop
Sets the dwell time, a length of time when high-slip braking is ending and during which the motor
speed decreases and runs at a stable speed. For a set length of time, the drive will hold the actual
output frequency at the minimum output frequency set in
E1-09
.
1.0 s
(0.0 - 10.0 s)
If there is too much inertia or when the motor is coasting to a stop after high-slip braking is complete, increase the
setting value. If the setting value is too low, machine inertia can cause the motor to rotate after high-slip braking is
complete.
■
n3-04: HSB Overload Time
No.
(Hex.)
Name
Description
Default
(Range)
n3-04
(058B)
Expert
HSB Overload Time
Sets the time used to detect
oL7 [High Slip Braking Overload]
, which occurs when the output
frequency does not change during high-slip braking. Usually it is not necessary to change this
parameter.
40 s
(30 - 1200 s)
If a force on the load side is rotating the motor or if there is too much load inertia connected to the motor, the
drive will detect
oL7
.
The current flowing to the motor from the load can overheat the motor and cause burn damage to the motor. Set
this parameter to prevent burn damage to the motor.
■
n3-13: OverexcitationBraking (OEB) Gain
No.
(Hex.)
Name
Description
Default
(Range)
n3-13
(0531)
OverexcitationBraking
(OEB) Gain
Sets the gain value that the drive multiplies by the V/f pattern output value during overexcitation
deceleration to calculate the overexcitation level.
1.10
(1.00 - 1.40)
The V/f pattern output value goes back to its usual level after the motor stops or accelerates again to the frequency
reference speed.
The best value of this parameter changes when the flux saturation characteristics of the motor change.
•
Gradually increase the value of
n3-13
to 1.25 or 1.30 to increase the braking power of Overexcitation
Deceleration. If the gain is too much, the motor can have flux saturation and cause a large quantity of current to
flow. This can increase the deceleration time.
•
Decrease the setting value if flux saturation causes overcurrent. If you increase the setting value, the drive can
detect
oC [Overcurrent]
,
oL1 [Motor Overload]
, and
oL2 [Drive Overload]
. Decrease the value of
n3-21 [HSB
Current Suppression Level]
to prevent
oC
and
oL
.
•
Regular use of overexcitation deceleration or extended periods of overexcitation deceleration can increase
internal motor temperatures. Decrease the setting value in these conditions.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...