YASKAWA
SIEPC71061753A GA500 Technical Manual
709
•
With a regenerative converter, for example D1000.
•
With a regenerative unit, for example R1000.
•
When connecting braking resistor options to the drive, for example CDBR units.
•
Without an internal braking transistor.
1 : Protection Enabled
Protects internal braking transistor when using a braking transistor or optional braking resistors.
■
L8-56: Stall P @ Accel Activation Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-56
(047D)
Expert
Stall P @ Accel Activation
Time
Sets the length time that the acceleration stall prevention function can continue to operate before
the drive detects an
STPo [Motor Step-Out Detected]
.
5000 ms
(100 - 5000 ms)
Note:
If this value is too small, it can cause incorrect detection of
STPo
. If this value is too large, the drive will not detect
STPo
.
■
L8-57: Stall Prevention Retry Counts
No.
(Hex.)
Name
Description
Default
(Range)
L8-57
(047E)
Expert
Stall Prevention Retry
Counts
Sets the number of times the acceleration stall prevention function can operate until speeds agree
before the drive detects an
STPo [Motor Step-Out Detected]
.
10
(1 - 10 times)
Note:
If this value is too small, it can cause incorrect detection of
STPo
. If this value is too large, the drive will not detect
STPo
.
■
L8-90: STPo Detection Level (Low Speed)
No.
(Hex.)
Name
Description
Default
(Range)
L8-90
(0175)
Expert
STPo Detection Level (Low
Speed)
Sets the detection level that the control fault must be equal to or more than to cause an
STPo
[Motor Step-Out Detected]
.
Determined by A1-02
(0 - 5000 times)
This function detects when PM motors are not synchronized.
The drive cannot detect when motors are not synchronized because the frequency reference is low during start up
and the motor is locked. If fault detection is necessary in these conditions, set the control fault detection level to
enable detection of desynchronization because of motor locking. Increase the setting in 5-unit increments.
■
L8-93: Low Speed Pull-out DetectionTime
No.
(Hex.)
Name
Description
Default
(Range)
L8-93
(073C)
Expert
Low Speed Pull-out
DetectionTime
Sets the length of time the drive will wait to start baseblock after detecting
LSo [Low Speed Motor
Step-Out]
.
1.0 s
(0.0 - 10.0 s)
Set this parameter to 0.0 to disable the function.
■
L8-94: Low Speed Pull-out Detect Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-94
(073D)
Expert
Low Speed Pull-out Detect
Level
Sets the detection level for
LSo [Low Speed Motor Step-Out]
as a percentage of
E1-04 [Maximum
Output Frequency]
.
3%
(0 - 10%)
■
L8-95: Low Speed Pull-out Amount
No.
(Hex.)
Name
Description
Default
(Range)
L8-95
(077F)
Expert
Low Speed Pull-out
Amount
Sets the average count of
LSo [Low Speed Motor Step-Out]
detections.
10
(1 - 50 times)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...