YASKAWA
SIEPC71061753A GA500 Technical Manual
665
12.9
L: Protection Functions
L parameters
set the following functions.
•
Motor Overload Protection
•
Operation During Momentary Power Loss
•
Stall Prevention
•
Speed Detection
•
Auto Restart
•
Detection of Overtorque/Undertorque
•
Torque Limit
•
Hardware Protection
◆
L1: Motor Protection
L1 parameters
set the motor overload protection function.
■
Motor Protection Using Positive Temperature Coefficient (PTC) Thermistors
The temperature resistance characteristics of three PTC thermistors in the motor stator winding protect the motor
from overheat.
A PLC thermistor must have the characteristics shown in
for each motor phase.
Figure 12.106 PTC Thermistor Temperature and Resistance
If the PTC input signal input to the drive is more than the overload alarm level, the drive detects
oH3 [Motor
Overheat (PTC Input)]
. The drive continues the operation set in
L1-03 [Motor Thermistor oH Alarm Select]
. By
default, the keypad shows oH3 and the drive continues operation.
The overheat fault level triggers an
oH4 [Motor Overheat Fault (PTC Input)]
fault, and outputs a fault signal. The
drive outputs a fault signal and uses the stop method set in
L1-04 [Motor Thermistor oH Fault Select]
to stop the
motor.
Note:
PTC is an acronym for Positive Temperature Coefficient.
■
L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name
Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
Determined by A1-02
(0 - 6)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
•
Output Current
•
Output Frequency
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...