12.2 A: Initialization Parameters
464
YASKAWA
SIEPC71061753A GA500 Technical Manual
User Parameter No.
Parameter No. Saved
Name
A2-08
E1-07
Mid Point A Frequency
A2-09
E1-08
Mid Point A Voltage
A2-10
E2-01
Motor Rated Current (FLA)
A2-11
H1-05
Terminal S5 Function Selection
A2-12
H1-06
Terminal S6 Function Selection
A2-13
H1-07
Terminal S7 Function Selection
A2-14
L5-01
Number of Auto-Restart Attempts
4 : HVAC Fan
The drive automatically sets the parameters in
for an HVAC fan application.
Table 12.10 Best Parameter Settings for HVAC Fan Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
b1-17
Run Command at Power Up
1: Accept Existing RUN Command
C6-01
Normal / Heavy Duty Selection
1: Normal Duty Rating
C6-02
Carrier Frequency Selection
3: 8.0 kHz (6.0 kHz for AOLV/PM)
H2-03
Term P2 Function Selection
39: Watt Hour Pulse Output
L2-01
Power Loss Ride Through Select
2: Enabled while CPU Power Active
L8-03
Overheat Pre-Alarm Selection
4: Operate at Reduced Speed (L8-19)
L8-38
Carrier Frequency Reduction
2: Enabled for All Speeds
The drive saves the parameters in
as User Parameters.
Table 12.11 Parameters Saved as User Parameters with the HVAC Fan Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-01
Frequency Reference Selection 1
A2-02
b1-02
Run Command Selection 1
A2-03
b1-03
Stopping Method Selection
A2-04
b1-04
Reverse Operation Selection
A2-05
C1-01
Acceleration Time 1
A2-06
C1-02
Deceleration Time 1
A2-07
C6-02
Carrier Frequency Selection
A2-08
d2-01
Frequency Reference Upper Limit
A2-09
d2-02
Frequency Reference Lower Limit
A2-10
E1-03
V/f Pattern Selection
A2-11
E1-04
Maximum Output Frequency
A2-12
E2-01
Motor Rated Current (FLA)
A2-13
H3-11
Terminal A2 Gain Setting
A2-14
H3-12
Terminal A2 Bias Setting
A2-15
L2-01
Power Loss Ride Through Select
A2-16
o4-12
kWh Monitor Initialization
5 : Air Compressor
The drive automatically sets the parameters in
for an air compressor application.
Table 12.12 Best Parameter Settings for Air Compressor Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...