A1-03 [Initialize Parameters]
•
A1-06 [Application Preset]
•
A1-07 [DriveWorksEZ Function Selection]
•
A2-01 to A2-32 [User Parameter 1 to 32]
Note:
•
Usually, the keypad will not show
A1-05
. To show and set
A1-05
, show
A1-04 [Password]
and then push
and
on the
keypad at the same time.
•
After you set
A1-05
, the keypad will not show it again until you enter the correct password in
A1-04
. Make sure that you remember the
A1-05
setting value. If you do not know the
A1-05
setting value, contact Yaskawa or your nearest sales representative.
•
When
A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization]
, the drive is initialized to
A1-05 = 0000
. Be sure to set the
password again when a password is necessary for the application.
•
Change the setting value in
A1-05
to change the password. The new setting value becomes the new password.
•
When you use the password to unlock and change a parameter, enter a value other than the password in
A1-04
to lock the parameter
again with the same password.
•
If
A1-04
≠
A1-05
, MEMOBUS Communication cannot read or write
A1-05
.
■
A1-06: Application Preset
WARNING!
Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06
≠
0), it changes the I/O terminal functions for
the drive and it can cause equipment to operate unusually. This can cause serious injury or death.
No.
(Hex.)
Name
Description
Default
(Range)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0
(0 - 8)
The drive software contains the application presets shown below. Set
A1-06
to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters that
you frequently use the application in parameters
A2-01 to A2-16 [User Parameters 1 to 16]
for easy configuration
and reference in Setup Mode.
•
Water supply pump
•
Conveyor
•
Exhaust fan
•
HVAC fan
•
Air compressor
•
Crane (hoist)
•
Crane (traveling)
Note:
•
Before you set
A1-06
, make sure that you set
A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization]
to initialize parameters.
•
After you set
A1-06
for a hoist application (
A1-06 = 6 or 7
), make sure that you do Auto-Tuning.
•
It is not possible to change the
A1-06
value. To set an application preset, first set
A1-03 = 2220
to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
If you set
A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms]
to set parameters to
A2-17 to A2-32 [User
Parameters 17 to 32]
automatically, the drive will reset these parameters when you change the
A1-06
setting.
0 : General-purpose
The drive saves the parameters in
as User Parameters.
Table 12.3 Parameters Saved as User Parameters with the General-purpose Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
A1-02
Control Method Selection
A2-02
b1-01
Frequency Reference Selection 1
A2-03
b1-02
Run Command Selection 1
A2-04
b1-03
Stopping Method Selection
A2-05
C1-01
Acceleration Time 1
A2-06
C1-02
Deceleration Time 1
A2-07
C6-01
Normal / Heavy Duty Selection
A2-08
C6-02
Carrier Frequency Selection
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...