12.11 o: Keypad-Related Settings
748
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
o5-05: Log Monitor Data 3
No.
(Hex.)
Name
Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
103
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-03 [Output Current]
, set
o5-05 = 103
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-06: Log Monitor Data 4
No.
(Hex.)
Name
Description
Default
(Range)
o5-06
(1556)
RUN
Log Monitor Data 4
Sets the data log monitor. This parameter is only available when using an LCD keypad.
107
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-07 [DC Bus Voltage]
, set
o5-06 = 107
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-07: Log Monitor Data 5
No.
(Hex.)
Name
Description
Default
(Range)
o5-07
(1557)
RUN
Log Monitor Data 5
Sets the data log monitor. This parameter is only available when using an LCD keypad.
108
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-08 [Output Power]
, set
o5-07 = 108
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-08: Log Monitor Data 6
No.
(Hex.)
Name
Description
Default
(Setting Range)
o5-08
(1558)
RUN
Log Monitor Data 6
Sets the data log monitor. This parameter is only available when using an LCD keypad.
000
(000, 101 - 999)
Note:
Set the
U monitor
number you want to log.
For example, to display
U1-01 [Frequency Reference]
, set
o5-08 = 101
. When it is not necessary to set a data log monitor, set this
parameter to
000
. You cannot set
U2 Monitors [Fault Trace]
or
U3 Monitors [Fault History]
.
■
o5-09: Log Monitor Data 7
No.
(Hex.)
Name
Description
Default
(Range)
o5-09
(1559)
RUN
Log Monitor Data 7
Sets the data log monitor. This parameter is only available when using an LCD keypad.
000
(000, 101 - 999)
Note:
Set the
U monitor
number you will log.
For example, to show
U1-01 [Frequency Reference]
, set
o5-09 = 101
. When it is not necessary to set data log monitor, set this
parameter to
000
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...