12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
661
Figure 12.103 Circuit Diagram When Used as the Sinking Input
■
H6-07: Terminal MP Frequency Scaling
No.
(Hex.)
Name
Description
Default
(Range)
H6-07
(0432)
RUN
Terminal MP Frequency
Scaling
Sets the frequency of the pulse train output signal used when the monitor set with
H6-06
[Terminal MP Monitor Selection]
is 100%.
1440 Hz
(0 - 32000 Hz)
When
H6-06 = 102 [Terminal MP Monitor Selection = Output Frequency]
and
H6-07 = 0
, the pulse train output
terminal MP outputs the same frequency as the drive output frequency.
■
H6-08: Terminal RP Minimum Frequency
No.
(Hex.)
Name
Description
Default
(Range)
H6-08
(043F)
Terminal RP Minimum
Frequency
Sets the minimum frequency of the pulse train signal that terminal RP can detect.
0.5 Hz
(0.1 - 1000.0 Hz)
•
When you input a pulse train frequency that is less than the value of
H6-08
, the pulse train input is 0.0 Hz.
•
Set
H6-01 [Terminal RP Pulse Train Function]
=
0 [Frequency Reference]
,
1 [PID Feedback Value]
, or
2 [PID
Setpoint Value]
to enable this parameter.
•
When
H6-01 = 3 [Speed Feedback (V/F Control)]
, the drive applies the setting of
F1-14 [Encoder Open-Circuit
Detect Time]
to the minimum frequency.
◆
H7: Virtual MFIO Selection
The virtual I/O function performs the following.
•
Inputs the result of the output from the MFDO terminal to the MFDI terminal without external wiring.
•
Inputs the result of the output from the MFAO terminal to the MFAI terminal without external wiring.
WARNING!
Sudden Movement Hazard. Before you do a test run, make sure that the setting values for virtual input and output
function parameters are correct. Virtual input and output functions can have different default settings and operation than wired
input and output functions. Incorrect function settings can cause serious injury or death.
Figure 12.104 Virtual Analog I/O Functional Block Diagram
Figure 12.105 Virtual Digital I/O Functional Block Diagram
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
H7-01
[Virtual Multi-Function
Input 1]
H7-11
[Virtual Output
1 Delay Time]
H7-10
[Virtual Multi-Function
Output 1]
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...