![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 145](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765145.webp)
4.11 Fine Tuning during Test Runs (Adjust the Control Function)
YASKAWA
SIEPC71061753A GA500 Technical Manual
145
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Speed response is slow.
•
Speed is not stable.
C3-02 [Slip Compensation Delay
Time]
•
If speed response is slow,
decrease the setting value in
increments of 10 ms.
•
If speed is not stable, increase
the value in increments of 10
ms.
200 ms
100 ms to 500 ms
Speed precision is unsatisfactory.
C3-01 [Slip Compensation Gain]
•
If speed is too slow, increase
the setting value in increments
of 0.1.
•
If speed is too fast, decrease
the setting value in increments
of 0.1.
1.0
0.5 - 1.5
•
The volume of the motor
excitation sound is too high.
•
Hunting or oscillation at low
speeds (10 Hz or lower)
C6-02 [Carrier Frequency
Selection]
•
If the volume of the motor
excitation sound is too high,
increase the carrier frequency.
•
If hunting or oscillation occur
at low speeds, decrease the
carrier frequency.
7(Swing PWM1)
0 to upper limit value
•
Torque at low speeds (10 Hz
or lower) is not sufficient.
speed response is slow.
•
Speed response is slow.
•
Large initial vibration at start
up.
•
E1-08 [Mid Point A Voltage]
•
E1-10 [Minimum Output
Voltage]
•
If torque or speed response are
slow, increase the setting
value.
•
If there is large initial
vibration at start up, decrease
the setting value
Note:
If you set the value too high,
the drive can output a large
torque reference although the
load is light.
•
E1-08: 12.0 V
•
E1-10: 2.5 V
Default s/- 2 V
*1
The default setting changes when the settings for
A1-02 [Control Method Selection]
and
o2-04 [Drive Model (KVA) Selection]
change.
*2
The default setting changes when the settings for
A1-02 [Control Method Selection]
and
E1-03 [V/f Pattern Selection]
change.
*3
The default setting changes when the settings for
C6-01 [Normal / Heavy Duty Selection]
and
o2-04
change.
*4
Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
◆
Fine-Tuning Open Loop Vector Control for PM Motors
Table 4.19 Parameters for Fine Tuning the Drive (
A1-02 = 5[OLV/PM]
)
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
Unsatisfactory motor
performance
E1-xx parameters, E5-xx
parameters
•
Check the settings for
E1-06,
E1-04 [Base Frequency,
Maximum Output Frequency]
.
•
Check the
E5-xx
and make
sure that all motor data has
been set correctly.
Note:
Do not set
E5-05 [PM Motor
Resistance (ohms/phase)]
to a
line-to-line resistance value.
•
Do Auto-Tuning.
-
-
Unsatisfactory motor torque and
speed response
n8-55 [Motor to Load Inertia
Ratio]
Adjust to match the load inertia
ratio of the motor and machine.
0
Near the actual load inertia ratio.
n8-45 [Speed Feedback Detection
Gain]
Decrease the setting value in
increments of 0.05.
0.80
-
C4-01 [Torque Compensation
Gain]
Adjust the setting value.
Note:
Setting this value too high can
cause overcompensation and
motor oscillation.
0.00
1.00
•
Oscillation when the motor
starts.
•
Motor stalls.
n8-51 [Pull-in Current @ Accel/
Decel]
Increase the setting value in
increments of 5%.
50%
-
•
b2-02 [DC Injection Braking
Current]
•
b2-03 [DC Inject Braking
Time at Start]
Use DC Injection Braking at start.
Note:
This can cause the motor to
rotate in reverse for
approximately 1/8 of a turn at
start.
•
b2-02: 50%
•
b2-03: 0.00 s
•
b2-02: Adjust as necessary.
•
b2-03: 0.5 s
n8-55 [Motor to Load Inertia
Ratio]
Increase the setting value.
Note:
When operating a single
motor or with a minimum
amount of inertia, setting this
value too high can cause
motor oscillation.
0
Near the actual load inertia ratio.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...