SIEPC71061753A GA500 Technical Manual
685
4 : Overexcitation/High Flux
Enables Overexcitation/High Flux and enables a shorter deceleration time than when
L3-04 = 0
.
Note:
•
If the overexcitation time is long and you decelerate frequently, the drive can detect
oL1 [Motor Overload]
faults. If the drive detects
oL1
, decrease the deceleration time or install a braking resistor to the drive.
•
The deceleration time during Overexcitation Deceleration changes when the motor characteristics and machine inertia change. Adjust
the
n3-13 [OverexcitationBraking (OEB) Gain]
and
n3-23 [Overexcitation Braking Operation]
levels. Refer to
“
n3: HighSlip/
OverexciteBraking
”
for more information about the overexcitation function.
5 : Overexcitation/High Flux 2
Enables Overexcitation/High Flux 2. This function decreases the possible deceleration time more than
Overexcitation/High Flux.
The drive decreases motor speed and tries to keep the DC bus voltage at the
L3-17
level.
If the drive detects
oL1
, decrease the values set in
n3-13
and
n3-21
. If the drive detects
ov
, increase the values set
in
C1-02, C1-04, C1-06, and C1-08 [Deceleration Times]
.
Note:
•
During Overexcitation/High Flux 2, the drive disables Hunting Prevention in V/f Control and also disables Speed Control that uses
torque limit in OLV Control.
•
Refer to
“
n3: HighSlip/OverexciteBraking
”
for more information about the overexcitation function.
7 : Overexcitation/High Flux 3
If you set
L3-04 = 7 [Overexcitation Braking 3]
, the overexcitation increases compared with
4 [Overexcitation/
High Flux]
. This can decrease the deceleration time.
Note:
When
L3-04 = 7
, the overexcitation current increases as compared with
4
. Motor load becomes larger, and it can cause
oL1 [Motor
Overload]
. When you can use
L3-04 = 4
to operate the drive, set
L3-04 = 4
.
■
L3-05: Stall Prevention during RUN
No.
(Hex.)
Name
Description
Default
(Range)
L3-05
(0493)
Stall Prevention during
RUN
Sets the function to enable and disable Stall Prevention During Run.
Determined by A1-02
(0 - Determined by A1-02)
Stall Prevention function during run prevents the motor from stalling by automatically reducing the speed when
an
oL1 [Motor Overload]
occurs while the motor is running at constant speed.
Note:
•
An output frequency less than 6 Hz disables Stall Prevention during Run. The setting values of
L3-05
and
L3-06 [Stall Prevent Level
during Run]
do not have an effect.
•
The setting range changes when the
A1-02 [Control Method Selection]
value changes:
–
A1-02 = 0, 5 [V/f, OLV/PM]
: 0 to 2
–
A1-02 =8 [EZOLV]
: 0, 3
0 : No
The drive runs at the set frequency reference. A heavy load can cause the motor to stall and trip the drive with
oC
[Overcurrent]
or
oL1
.
1 : Deceleration Time 1 (C1-02)
The drive will decelerate for the time set in
C1-02 [Deceleration Time 1]
when the current is more than the Stall
Prevention level set in
L3-06
. When the current level is less than the
“
L3-06
setting value - 2%
”
for 100 ms, the
drive accelerates again for the acceleration time applicable at that time until it is at the set frequency.
2 : Deceleration Time 2 (C1-04)
This setting functions the same as
Setting 1 [Deceleration Time 1 (C1-02)]
. When you enable the Stall Prevention
function, the drive decelerates in the time set in
C1-04 [Deceleration Time 2]
.
3 : Intelligent (Ignore Decel Ramp)
Enabled when
A1-02 = 8 [EZOLV]
. The drive operates with the largest possible output current to prevent motor
stalling.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...