540
YASKAWA
SIEPC71061753A GA500 Technical Manual
12.5
d: References
d parameters [References]
set the frequency reference input method and dead band range. They also set torque
control, field weakening, and field forcing functions.
WARNING!
Sudden Movement Hazard. Use fast stop circuits to safely and quickly stop the drive. After you wire the fast stop
circuits, you must check their operation. Test the operation of the fast stop function before you use the drive. If you do not test
the fast stop circuit before you operate the drive, it can cause serious injury or death.
WARNING!
Sudden Movement Hazard. When you use the drive in a lifting application, you must also install external safety
circuitry. The drive does not have protection against accidental load drops in lifting applications. Install electrical and/or
mechanical safety circuit mechanisms that are isolated from the drive circuitry. If you do not use external safety circuitry, the
drive could drop the load and cause serious injury or death.
◆
d1: Frequency Reference
shows the frequency reference input method, command source selection method, and priority
descriptions.
Figure 12.48 Frequency Reference Setting Hierarchy
■
Multi-Step Speed Operation
The drive has a multi-step speed operation function that can set many frequency references in advance. Set
frequency references in
d1-xx parameters
. You can select the set frequency references with MFDI signals from an
external source. Activate and deactivate the digital input to select the frequency reference to change the motor
speed in steps. You can use the 16-step frequency reference and one Jog Frequency Reference (JOG command) to
switch the speed to the maximum 17-step speeds.
Note:
•
The Jog Frequency Reference (JOG command) overrides all other frequency references.
•
You can use the MFDI to switch the frequency reference when the motor is running. The drive will apply the enabled acceleration and
deceleration times.
•
The default settings for Multi-Step Speed Reference 1 (master frequency reference) and Multi-Step Speed Reference 2 (auxiliary
frequency reference) are the analog frequency reference.
Also, voltage command input terminal A1 and current input terminal A2 for Multi-Step Speed Reference 1 (master frequency
reference) are added internally by default. The drive uses Multi-Step Speed Reference 1 when the signal is connected to an analog
input terminal.
■
Setting Procedures for Multi-step Speed Operation
Use an Analog Input as Reference 1 and 2
This section gives information about the procedures to set these examples:
•
Multi-Step Speed 6 (6 types of frequency references)
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...