You can use
to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL
Mode is selected,
on the keypad will come on.
WARNING!
Sudden Movement Hazard. If you change the control source when b1-07 = 1 [LOCAL/REMOTE Run Selection =
Accept Existing RUN Command], the drive can start suddenly. Before you change the control source, remove all personnel from
the area around the drive, motor, and load. Sudden starts can cause serious injury or death.
WARNING!
Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/
RE Key Function Selection] or b1-07 [LOCAL/REMOTE Run Selection]. Sudden starts can cause serious injury or death. If b1-
07 = 1 [Accept Existing RUN Command] and there is an active Run command when you switch from LOCAL to REMOTE Mode,
the drive can start suddenly.
Table 12.73 Function Settings with o2-01 and b1-07
Function Selection
LOCAL/REMOTE Run Selection
Switching from LOCAL Mode to
REMOTE Mode
Switching from REMOTE Mode to
LOCAL Mode
o2-01 = 0 [Disabled]
b1-07 = 0 [Disregard Existing RUN
Command]
The drive will not switch modes.
The drive will not switch modes.
b1-07 = 1 [Accept Existing RUN
Command]
o2-01 = 1 [Enabled]
b1-07 = 0 [Disregard Existing RUN
Command]
The drive will not start operating although
the Run command is active. When you set
Run command to active again, the drive
will start to run.
The drive cannot operate because the Run
command is not enabled.
b1-07 = 1 [Accept Existing RUN
Command]
When the Run command is active, the
drive will start to run immediately when
the mode switches from LOCAL to
REMOTE.
The drive cannot operate because the Run
command is not enabled.
■
o2-02: STOP Key Function Selection
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-02
(0506)
STOP Key Function
Selection
Sets the function to use
on the keypad to stop the drive when the Run command source
for the drive is REMOTE (external) and not assigned to the keypad.
1
(0, 1)
0 : Disabled
1 : Enabled
stays enabled when the Run command source has not been assigned to the keypad.
To start the drive again after you push
to stop operation, turn the external Run command OFF and ON
again.
■
o2-03: User Parameter Default Value
No.
(Hex.)
Name
Description
Default
(Range)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to use
during initialization.
0
(0 - 2)
When you set
o2-03 = 1 [Set defaults]
, the drive saves changed parameter settings as user parameter setting
values in a part of the memory that is isolated from drive parameters.
When you set
A1-03 = 1110 [Initialize Parameters = User Initialization]
to initialize the drive, the drive resets the
internal parameter setting values to those user parameter setting values.
0 : No change
1 : Set defaults
Saves changed parameter setting values as user default settings.
Set
o2-03 = 1
then push
to save the user parameter setting values. After the drive saves the setting value,
o2-
03
automatically resets to
0
.
2 : Clear all
Deletes all of the saved user parameter setting values.
Set
o2-03 = 2
then push
to clear the user parameter setting values. The drive will automatically reset
o2-03
to
0
. If you delete the user parameter setting values, you cannot set
A1-03 = 1110
to initialize parameters.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...