YASKAWA
SIEPC71061753A GA500 Technical Manual
517
When you use a motor from a different manufacturer, increase the setting value in 5% increments to find the
minimum value for
U1-08 [Output Power]
at light loads.
When you decrease the setting value, it decreases the output voltage and decreases power consumption. If the
setting value is too low, the motor will stall.
Note:
When you do Rotational Auto-Tuning, the drive will automatically set the energy-saving coefficient.
■
b8-05: Power Detection Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
b8-05
(01D0)
Expert
Power Detection Filter
Time
Sets the time constant to measure output power.
20 ms
(0 - 2000 ms)
Decrease the setting value to increase responsiveness to load changes. If you set the value too low during
operation at light loads, motor speed is not stable.
■
b8-06: Search Operation Voltage Limit
No.
(Hex.)
Name
Description
Default
(Range)
b8-06
(01D1)
Expert
Search Operation Voltage
Limit
Sets the voltage limit for Search Operation as a percentage of the motor rated voltage.
0%
(0 - 100%)
The Search Operation changes the output voltage in small increments to find a setpoint at which the drive can use
minimum power to operate.
Set this parameter to 0 to disable Search Operation. This will not disable Energy-saving control.
If the setting value is too low, the motor will stall when loads suddenly increase.
■
b8-16: PM E-Save Coefficient Ki
No.
(Hex.)
Name
Description
Default
(Range)
b8-16
(01F8)
Expert
PM E-Save Coefficient Ki
Sets torque linearity. This parameter uses the Ki value from the motor nameplate. Usually it is not
necessary to change this setting.
1.00
(0.00 - 3.00)
When
b8-16 = 1.00
(default), the drive will automatically calculate and control the energy-saving coefficient. If
the motor nameplate has a description for
“
Ki
”
, set this parameter to the Ki value.
Do this procedure to prevent oscillation when you set
b8-01 = 1 [Energy Saving Control Selection = Enabled]
.
1. Check
U5-21 [Energy Save Coeff Ki]
and make sure that it aligns with the Ki value on the motor nameplate.
2. If the numbers are different, set
b8-16
to the Ki value on the motor nameplate.
■
b8-17: PM E-Save Coefficient Kt
No.
(Hex.)
Name
Description
Default
(Range)
b8-17
(01F9)
Expert
PM E-Save Coefficient Kt
Sets torque linearity. This parameter uses the Kt value from the motor nameplate. Usually it is not
necessary to change this setting.
1.00
(0.00 - 3.00)
When
E5-01 = 1xxx [PM Motor Code Selection = Yaskawa SSR1 series IPM motor]
, the drive automatically
calculates the energy-saving coefficient Kt and uses that value to control operation.
Do this procedure to prevent oscillation when you set
b8-01 = 1 [Energy Saving Control Selection = Enabled]
.
1. Check
U5-22 [Energy Save Coeff Kt]
and make sure that it aligns with the Kt value on the motor nameplate.
2. If the numbers are different, set
b8-17
to the Kt value on the motor nameplate.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...