138
YASKAWA
SIEPC71061753A GA500 Technical Manual
Control Tuning automatically sets the parameters in
to the best values.
Table 4.15 Parameters set in Control Tuning
Parameters Automatically Set
Deceleration Rate Tuning
KEB Tuning
C1-02 [Deceleration Time 1]
x
-
C1-08 [Deceleration Time 4]
x
-
C1-09 [Fast Stop Time]
-
x
L2-06 [Kinetic Energy Backup Decel Time]
-
x
L3-25 [Load Inertia Ratio]
-
x
*1
The drive automatically sets
C1-08 [Deceleration Time 4]
only when
C1-11 [Accel/Decel Time Switchover Freq] ≠ 0
.
*2
When
L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1]
, the drive will automatically adjust
C1-09 [Fast
Stop Time]
and will not adjust
L2-06 [Kinetic Energy Backup Decel Time]
. If you must not change the Fast Stop time, do not do KEB
Tuning.
*3
When
L2-29 = 1, 2, or 3 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2, System KEB Ride-Thru 1, or System
KEB Ride-Thru 2]
, the drive will automatically adjust
L2-06 [Kinetic Energy Backup Decel Time]
.
◆
Precautions before Auto-Tuning
Examine the topics in this section before you start Auto-Tuning.
■
Prepare for Basic Auto-Tuning
•
You must input data from the motor nameplate or motor test report to do Auto-Tuning. Make sure that this data
is available before you do Auto-Tuning.
•
For best performance, make sure that the drive input supply voltage is equal to or more than the motor rated
voltage.
Note:
Better performance is possible when you use a motor with a rated voltage that is less than the input supply voltage (by 20 V for 200 V
class models or by 40 V for 400 V class models). This is very important when you operate the motor at more than 90% of base speed,
where high torque precision is necessary. If the input power supply is equal to the motor rated voltage, the drive output voltage will not
be sufficient and performance will decrease.
•
Push
on the keypad to cancel Auto-Tuning.
•
If a Safe Disable input signal is input to the drive during Auto-Tuning, Auto-Tuning measurements will not
complete successfully. If this occurs, cancel the Auto-Tuning, then do it again.
•
shows the status of multi-function input/output terminals during Auto-Tuning.
Table 4.16 Status of Input/Output Terminals during Auto-Tuning
Auto-Tuning Type
Mode
Parameter
Multi-Function
Input
Multi-Function Output
Induction Motor Auto-
Tuning
Rotational
Rotational Auto-Tuning
T1-01 = 0
Disabled
Functions the same as during usual operation.
Stationary
Stationary Auto-Tuning 1
T1-01 = 1
Disabled
Keeps the status at the start of Auto-Tuning.
Line-to-Line Resistance
T1-01 = 2
Disabled
Keeps the status at the start of Auto-Tuning.
PM Motor Auto-Tuning
Rotational
PM Motor Code Selection
T2-01 = 4
Disabled
Functions the same as during usual operation.
Stationary
Manual Entry w/ Motor Data
Sheet
T2-01 = 0
Disabled
Disabled
PM Stationary Auto-Tuning
T2-01 = 1
Disabled
Keeps the status at the start of Auto-Tuning.
PM Stationary Auto-Tuning for
Stator Resistance
T2-01 = 2
Disabled
Keeps the status at the start of Auto-Tuning.
High Frequency Injection
T2-01 = 5
Disabled
Keeps the status at the start of Auto-Tuning.
EZ Tuning
Stationary
Motor Parameter Setting
T4-01 = 0
Disabled
Disabled
Line-to-Line Resistance
T4-01 = 1
Disabled
Keeps the status at the start of Auto-Tuning.
ASR and Inertia Tuning
Rotational
Deceleration Rate Tuning
T3-00 = 2
Disabled
Functions the same as during usual operation.
KEB Tuning
T3-00 = 3
Disabled
Functions the same as during usual operation.
*1
When you set a terminal to
H2-xx = E [MFDO Function Selection = Fault]
, it will function the same as during usual operation.
WARNING!
Crush Hazard. Wire a sequence that will not let a multi-function output terminal open the holding brake during
Stationary Auto-Tuning. If the holding brake is open during Stationary Auto-Tuning, it can cause serious injury or death.
WARNING!
Sudden Movement Hazard.. Before you do Rotational Auto-Tuning, disconnect the load from the motor. The load
can move suddenly and cause serious injury or death.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...