SIEPC71061753A GA500 Technical Manual
497
■
b3-56: InverseRotationSearch WaitTime
No.
(Hex.)
Name
Description
Default
(Range)
b3-56
(3126)
InverseRotationSearch
WaitTime
Sets the wait time until the drive starts inverse rotation search after it completes forward search
when you do inverse rotation search during Current Detection Speed Search.
Determined by o2-04
(0.1 - 5.0 s)
■
b3-61: Initial Pole Detection Gain
No.
(Hex.)
Name
Description
Default
(Range)
b3-61
(1B96)
Expert
Initial Pole Detection
Response Gain
Sets the responsiveness for initial motor magnetic pole calculation when
A1-02 = 6 [Control
Method Selection = AOLV/PM]
. Set
b3-61 > 0.0
for an ordinary IPM motor.
5.0
(-20.0 - +20.0)
Used when
n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection]
. Sets the responsiveness for
initial motor magnetic pole calculation. Set this parameter to a positive value for an ordinary monitor. When you
use High Frequency injection Tuning, it will automatically set this parameter.
◆
b4: Timer Function
The drive uses timers to delay activating and deactivating MFDO terminals.
Timers prevent sensors and switches from making chattering noise.
There are two types of timers:
•
Timers that set a delay for timer inputs and timer outputs.
These timers delay activating and deactivating of the MFDIs and MFDOs.
To enable this function, set
H1-xx = 18 [MFDI Function Selection = Timer Function], and set H2-01 to H2-03
= 12 [MFDO Function Selection = Timer Output]
.
•
Timers that set a delay to activate and deactivate MFDO terminals.
These timers delay activating and deactivating MFDO terminals.
To enable this function, set delay times in parameters
b4-03 to b4-08
.
■
Timer Function Operation
•
Timers that Set a Delay for Timer Inputs and Timer Outputs
Triggers timer output if the timer input is active for longer than the time set in
b4-01 [Timer Function ON-Delay
Time]
. Triggers timer output late for the time set in
b4-02 [Timer Function OFF-Delay Time]
.
shows an example of how the timer function works.
Figure 12.26 Example of Timer Function Operation
•
Setting On/Off-delay Time for MFDO
uses H2-01 terminals to show an example of how the timer function works. Use
b4-03 [Terminal
M1-M2 ON-Delay Time]
and
b4-04 [Terminal M1-M2 OFF-Delay Time]
to set this function.
Figure 12.27 Example of How the Timer Function Works with H2-01 Terminals
Note:
When the terminal is triggered, it continues for a minimum of 100 ms. The on/off-delay time of MFDO terminal does not have an effect.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...