574
YASKAWA
SIEPC71061753A GA500 Technical Manual
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
■
E9-03: Rated Speed
No.
(Hex.)
Name
Description
Default
(Range)
E9-03
(11E6)
Rated Speed
Sets the rated rotation speed of the motor.
Determined by E9-01
(100 - 7200 min
-1
)
EZ Tuning automatically sets this parameter to the value of [Rated Speed].
Note:
Set
E9-01 = 0 [Motor Type Selection = Induction (IM)]
before you set this parameter.
■
E9-04: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E9-04
(11E7)
Base Frequency
Sets the rated frequency of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
Note:
The unit of measure changes when the setting of
o1-04 [V/f Pattern Display Unit]
.
EZ Tuning automatically sets this parameter to the value of [Base Frequency].
■
E9-05: Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E9-05
(11E8)
Motor Rated Voltage
Sets the rated voltage of the motor.
200 V Class: 200.0 V, 400
V: 400.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
EZ Tuning automatically sets this parameter to the value of [Base Voltage].
■
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1 A: 2056 to 2082, 4031 to 4060
The setting value of
E9-06
is the reference value for motor protection. Enter the motor rated current written on the
motor nameplate. Auto-Tuning the drive will automatically set
E9-06
to the value input for
T4-07 [Motor Rated
Current]
.
■
E9-07: Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E9-07
(11EA)
Motor Rated Power
Sets the motor rated output in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by E9-02 and
o2-04
(0.00 - 650.00 kW)
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Power (kW)].
■
E9-08: Motor Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E9-08
(11EB)
Motor Pole Count
Sets the number of motor poles.
4
(2 to 120)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...