374
YASKAWA
SIEPC71061753A GA500 Technical Manual
Setting Value
Function
Description
Ref.
9F
DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
ON : No
OFF : Yes
Note:
Set
A1-07 = 2 [DriveWorksEZ Function Selection = Digital input]
to enable this function.
101 to 19F
Inverse Input of 1 to 9F
Sets the function of the selected MFDI to operate inversely. To select the function, enter
“
1xx
”
, where the
“
xx
”
is
the function setting value.
Note:
You cannot use inverse input for all functions. Refer to
for more information.
◆
H2: Digital Outputs
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H2-01
(040B)
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in
through mode.
E
(0 - 1FF)
H2-02
(040C)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in
through mode.
0
(0 - 1FF)
H2-03
(040D)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in
through mode.
2
(0 - 1FF)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when
H2-01 to H2-03 = 39 [MFDO Function
Selection = Watt Hour Pulse Output]
.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
H2-07
(0B3A)
Modbus Register 1
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-09
(0B3C)
Modbus Register 2
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-20
(1540)
Comparator 1 Monitor
Selection
Sets the monitor number for comparator 1. Set the
x-xx
part of the
Ux-xx [Monitor]
. For
example, set
H2-20 = 102
to monitor
U1-02 [Output Frequency]
.
102
(000 - 999)
H2-21
(1541)
Comparator 1 Lower
Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output
for the monitor selected in
H2-20 [Comparator 1 Monitor Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
H2-22
(1542)
Comparator 1 Upper
Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output
for the monitor selected in
H2-20 [Comparator 1 Monitor Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output
for the monitor selected in
H2-20 [Comparator 1 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
H2-24
(1544)
Comparator 1 On-Delay
Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
H2-25
(1545)
Comparator 1 Off-Delay
Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the
x-xx
part of the
Ux-xx [Monitor]
. For
example, set
H2-26 = 103
to monitor
U1-03 [Output Current]
.
103
(000 - 999)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...