YASKAWA
SIEPC71061753A GA500 Technical Manual
267
Code
Name
Causes
Possible Solutions
Electrical interference caused a drive malfunction.
•
Examine the control circuit lines, main circuit lines, and
ground wiring, and decrease the effects of electrical
interference.
•
Make sure that a magnetic contactor is not the source of the
electrical interference, then use a Surge Protective Device if
necessary.
•
Set
L5-01 ≠ 0 [Number of Auto-Restart Attempts ≠ 0 times]
.
Note:
•
The drive detects this error if the DC bus voltage is more than the
ov
detection level when the Run command has not been input (while the drive is stopped).
•
The
ov
detection level is approximately 410 V with 200 V class drives. The detection level is approximately 820 V for 400 V class drives.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
PASS
Modbus Communication Test
The MEMOBUS/Modbus communications test is
complete.
The
PASS
display will turn off after communications test mode is
cleared.
Code
Name
Causes
Possible Solutions
PF
Input Phase Loss
There is a phase loss in the drive input power.
Correct all wiring errors with the main circuit power supply.
Loose wiring in the input power terminals.
Tighten the screws to the correct tightening torque.
The drive input power voltage is changing too
much.
•
Examine the supply voltage for problems.
•
Make the drive input power stable.
Unsatisfactory balance between voltage phases.
•
Examine the supply voltage for problems.
•
Make the drive input power stable.
•
If the supply voltage is good, examine the magnetic contactor
on the main circuit side for problems.
The main circuit capacitors have become
unserviceable.
•
Examine the capacitor maintenance time in monitor
U4-05
[CapacitorMaintenance]
.
•
If
U4-05
is more than 90%, replace the capacitor. Contact
Yaskawa or your nearest sales representative for more
information.
•
Examine the supply voltage for problems.
•
Re-energize the drive.
•
If the alarm stays, replace the circuit board or the drive. For
information about replacing the control board, contact
Yaskawa or your nearest sales representative.
Note:
•
The drive detects this error if the DC bus voltage changes irregularly without regeneration.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
Use
L8-05 [Input Phase Loss Protection Sel]
to enable and disable
PF
detection.
Code
Name
Causes
Possible Solutions
PGo
Encoder (PG) Feedback Loss
The encoder cable is disconnected or wired
incorrectly.
Examine for wiring errors or disconnected wires in the encoder
cable, and repair problems.
The encoder is not receiving power.
Examine the encoder power supply.
The holding brake is stopping the motor.
Release the holding brake.
Note:
•
The drive detects this error if it does not receive the speed detection pulse signal from the encoder in the detection time set in
F1-14 [Encoder Open-Circuit Detect Time]
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F1-02 [PG Open Circuit Detection Select]
.
Code
Name
Causes
Possible Solutions
rUn
Motor Switch during Run
The drive received a
Motor 2 Selection [H1-xx =
16]
during run.
Make sure that the drive receives the Motor 2 Selection while the
drive is stopped.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
SE
Modbus Test Mode Error
MEMOBUS/Modbus communications self-
diagnostics
[H1-xx = 67]
was done while the drive
was running.
Stop the drive and do MEMOBUS/Modbus communications self-
diagnostics.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
SToF
Safe Torque OFF Failure
One of the two terminals H1-HC and H2-HC
received the Safe Disable input signal.
The Safe Disable input signal is wired incorrectly.
•
Make sure that the Safe Disable signal is input from an
external source to terminals H1-HC or H2-HC.
•
When the Safe Disable function is not in use, connect
terminals H1-HC and H2-HC.
There is internal damage to one Safe Disable
channel.
Replace the board or the drive. For information about replacing
the control board, contact Yaskawa or your nearest sales
representative.
Note:
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...