YASKAWA
SIEPC71061753A GA500 Technical Manual
503
Purpose
Procedure
Results
Prevent overshoot.
•
Set
b5-05 [Derivative Time (D)]
to a smaller
value.
•
Set
b5-03 [Integral Time (I)]
to a larger value.
Quickly stabilize control.
•
Set
b5-05 [Derivative Time (D)]
to a larger
value.
•
Set
b5-03 [Integral Time (I)]
to a smaller value.
Prevent long-cycle oscillations.
Set
b5-03 [Integral Time (I)]
to a larger value.
Prevent short-cycle oscillations.
•
Set
b5-05 [Derivative Time (D)]
to a smaller
value.
•
If you set
b5-05 = 0.00 [Derivative Time (D) =
disabling D control]
and it does not stop
oscillation, then set
b5-02 [Proportional Gain
(P)]
to a smaller value or set
b5-08 [PID
Primary Delay Time Constant]
to a larger value.
■
EZ Sleep/Wake-up Functionality
Set
b5-89 = 1 [Sleep Method Selection = EZ Sleep/Wake-up]
to enable the EZ Sleep/Wake-up function.
Note:
•
When
b5-89 = 0 [Sleep Mode Selection = Standard]
, the EZ Sleep function and related parameters are disabled. Parameter
b5-91 [EZ
Minimum Speed]
is not included in this rule.
•
Set
b5-89 = 1
to disable
b5-15 [PID Sleep Function Start Level]
.
Configuration Parameter
Description
b5-90 [EZ Sleep Unit]
Sets the unit of measure for
b5-92 [EZ Sleep Level]
. When
b5-90 = 0 [0.1Hz units]
, the setting range of
b5-
91 [EZ Minimum Speed]
is 0.0 to 590.0 Hz. When
b5-90 = 1 [rev/min]
, the setting range is 0 to 35400 min
-1
(r/min).
Note:
When you change
b5-90
, the value of
b5-92
is not automatically updated.
b5-91 [EZ Minimum Speed]
This parameter sets the lower limit for PID output. The drive uses the largest value of
b5-91
,
b5-34 [PID
Output Lower Limit]
, and
d2-02 [Frequency Reference Lower Limit]
to internally set the lower limit of PID
output. The
b5-89
setting does not have an effect.
b5-92 [EZ Sleep Level]
When the output frequency or motor speed is less than the value of
b5-92
for longer than the value of
b5-93
[EZ Sleep Time]
, the drive does to sleep.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...