692
YASKAWA
SIEPC71061753A GA500 Technical Manual
Setting Value
Function
15
Frequency Detection 3
Setting Value
Function
16
Frequency Detection 4
•
When you use these functions for MEMOBUS monitor data:
Register No.
Description
002CH
Drive Status 2
bit2
Speed agreement
1: During agreement
bit3
User-defined speed agreement
1: During agreement
bit4
Frequency Detection 1
1: Output frequency ≤ L4-01
bit5
Frequency Detection 2
1: Output frequency ≥ L4-01
004BH
U1-12 [Drive Status]
bit4
1: During speed agreement
•
When you use these functions for monitor parameters:
No.
(Hex.)
Name
Description
U1-12
(004B)
Drive Status
bit 4: During speed agreement
◆
L5: Fault Restart
The Auto Restart function tries to keep machines operating when the drive detects a transient fault.
The drive can do a self-diagnostic check and continue the operation after a fault. If the cause of the fault goes
away, the drive does speed search and restarts. It will not stop and the drive will not record a fault history. Use
L5-
02 [Fault Contact at Restart Select]
to select the operation of fault relay signals during Auto Restart operation.
Sets if the drive will do Auto Restart and the number of times the drive will try to do Auto Restart in a set time. If
the number of Auto Restart tries is more than the set value during the set time, drive output shuts off and operation
stops. If this happens, remove the cause of the fault and manually restart the drive.
WARNING!
Sudden Movement Hazard. Do not use the fault restart function in hoist or lifting applications. Failure to obey can
cause death or serious injury.
The drive can do Auto Restart when these faults occur:
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Table 12.69 List of Faults during which Auto Restart is Available
Fault
Name
Parameters to Disable
Auto Restart
GF
Ground Fault
L5-08
LF
Output Phase Loss
-
oC
Overcurrent
-
oH1
Heatsink Overheat
L5-08
oL1
Motor Overload
L5-07
oL2
Drive Overload
L5-07
oL3
Overtorque Detection 1
L5-07
oL4
Overtorque Detection 2
L5-07
Fault
Name
Parameters to Disable
Auto Restart
ov
Overvoltage
L5-08
PF
Input Phase Loss
-
rH
Braking Resistor Overheat
-
rr
Dynamic Braking
Transistor Fault
-
STPo
Motor Step-Out Detected
-
Uv1
DC Bus Undervoltage
L5-08
*1
Uv1
is the target for the auto restart process when
L2-01 = 1, 2, 3, or 4 [Power Loss Ride Through Select = Enabled for L2-02 Time,
Enabled while CPU Power Active, Kinetic Energy Backup: L2-02, or Kinetic Energy Backup: CPU Power]
.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...