Register No.
(Hex.)
Description
00EA
Fault Description 11
bit 0
TiM [Keypad Time Not Set]
bit 1
bAT [Keypad Battery Low Voltage]
bit 2- D
Reserved
bit E
SCF [Safety Circuit Fault]
bit F
Reserved
00EB - 00ED
Reserved
00EE
Fault Description 12
bit 0 - 2
Reserved
bit 3
CP1 [Comparator 1 Limit Fault]
bit 4
CP2 [Comparator 2 Limit Fault]
bit 5
bCE [Bluetooth Communication Fault]
bit 6 - F
Reserved
00EF - 00FA
Reserved
00FB
Output Current
Note:
The unit of display is different for different models.
2001 to 2042, B001 to B018, 4001 to 4023: 0.01 A
2056 to 2082, 4031 to 4060: 0.1 A
■
Broadcast Messages
Broadcast messages are available as read-only.
The undefined bit signal in the broadcast operation signal uses the local data signal.
Table 6.13 Broadcast Messages for MEMOBUS/Modbus Communication
Register No.
(Hex.)
Description
0001
Operation signal
bit 0
Run command
1: Run, 0: Stop
bit 1
Reverse run command
1: Reverse, 0: Forward run
bit 2 - 3
Reserved
bit 4
External fault
1: EF0 [Option Card External Fault]
bit 5
Fault Reset
1: Reset command
bit 6 - B
Reserved
bit C
MFDI terminal S5 input
bit D
MFDI terminal S6 input
bit E
MFDI terminal S7 input
bit F
Reserved
0002
Frequency reference
30000/100%
■
Fault Trace/Fault History Contents
shows the fault codes that the commands from monitors
[U2-xx, U3-xx]
read.
Table 6.14 Fault Trace/Fault History Contents
Fault Code
(Hex.)
Name
0002
Uv1 [DC Bus Undervoltage]
0003
Uv2 [Control Power Undervoltage]
Fault Code
(Hex.)
Name
0004
Uv3 [Soft Charge Answerback Fault]
0005
SC [Short Circuit/IGBT Failure]
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...