F6-20: MECHATROLINK Station Address
No.
(Hex.)
Name
Description
Default
(Range)
F6-20
(036B)
MECHATROLINK Station
Address
Sets the station address for MECHATROLINK communication. Change the parameter then cycle
power on the drive.
0021h
(MECHATROLINK-II:
0020h - 003Fh,
MECHATROLINK-III:
0003h - 00EFh)
Note:
•
The setting range changes if using MECHATROLINK-II or MECHATROLINK-III:
–
MECHATROLINK-II (SI-T3) range: 20 to 3F
–
MECHATROLINK-III (SI-ET3) range: 03 to EF
•
Be sure to set a node address that is different than all other node addresses. Incorrect parameter settings will cause
AEr [Station
Address Setting Error]
errors and the L.ERR LED on the option will come on.
•
The drive detects
AEr
errors when the station address is 20 or 3F.
■
F6-21: MECHATROLINK Frame Size
No.
(Hex.)
Name
Description
Default
(Range)
F6-21
(036C)
MECHATROLINK Frame
Size
Sets the frame size for MECHATROLINK communication. Restart the drive after you change the
parameter setting.
0
(0, 1)
0 : 32byte (M-2) / 64byte (M-3)
1 : 17byte (M-2) / 32byte (M-3)
■
F6-22: MECHATROLINK Link Speed
No.
(Hex.)
Name
Description
Default
(Range)
F6-22
(036D)
MECHATROLINK Link
Speed
Sets the communications speed for MECHATROLINK-II. Restart the drive after you change the
parameter setting.
0
(0, 1)
Note:
This parameter is only available with the MECHATROLINK-II option.
0 : 10 Mbps
1 : 4 Mbps
■
F6-23: MECHATROLINK Monitor Select (E)
No.
(Hex.)
Name
Description
Default
(Range)
F6-23
(036E)
MECHATROLINK
Monitor Select (E)
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive operation control
command) and INV_I/O (drive I/O control command). Restart the drive after you change the
parameter setting.
0000h
(0000h - FFFFh)
To enable the MEMOBUS register set in
F6-23
, set SEL_MON2/1 to 0EH or set SEL_MON 3/4 and SEL_MON
5/6 to 0EH. Bytes of the response data enable the MEMOBUS register content that was set in
F6-23
.
■
F6-24: MECHATROLINK Monitor Select (F)
No.
(Hex.)
Name
Description
Default
(Range)
F6-24
(036F)
MECHATROLINK
Monitor Select (F)
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive operation control
command) and INV_I/O (drive I/O control command). Restart the drive after you change the
parameter setting.
0000h
(0000h - FFFFh)
To enable the MEMOBUS register set in
F6-24
, set SEL_MON2/1 to 0FH or set SEL_MON3/4 and SEL_MON
5/6 to 0FH. Bytes of the response data enable the MEMOBUS register content that was set
F6-24
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...