![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 488](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765488.webp)
488
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
b2-08: Magnetic Flux Compensation Value
No.
(Hex.)
Name
Description
Default
(Range)
b2-08
(0190)
Magnetic Flux
Compensation Value
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial
Excitation) as a percentage of
E2-03 [Motor No-Load Current]
.
0%
(0 - 1000%)
This parameter is effective when you start a high-capacity motor (a motor with a large secondary circuit time
constant). This function can quickly increase motor flux to make high starting torque (a process called initial
excitation).
The current level for DC Injection Braking at start changes linearly from the setting of
b2-08
to the setting of
b2-
03
as shown in
Figure 12.21 DC Current Level during DC Injection Braking at Start
Note:
•
If
b2-08 < 100%
, flux will develop very slowly.
•
When
b2-08 = 0%
, the DC current level will be the DC Injection current set in
b2-02 [DC Injection Braking Current]
.
•
If
b2-08
is set too high, DC Injection Braking at start can cause a large noise. Adjust
b2-08
to decrease the volume to the permitted
level.
■
b2-12: Short Circuit Brake Time @ Start
No.
(Hex.)
Name
Description
Default
(Range)
b2-12
(01BA)
Short Circuit Brake Time @
Start
Sets the Short Circuit Braking time at start.
0.00 s
(0.00 - 25.50 s)
This function stops and restarts a coasting PM motor. The drive short circuits all the three motor phases to make
braking torque in the motor.
Set this parameter to 0.00 to disable the function.
Note:
•
Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external
forces.
•
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
■
b2-13: Short Circuit Brake Time @ Stop
No.
(Hex.)
Name
Description
Default
(Range)
b2-13
(01BB)
Short Circuit Brake Time @
Stop
Sets the Short Circuit Braking time at stop.
A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50
s
(0.00 - 25.50 s)
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
Short Circuit Braking operates for the time set in
b2-13
when output frequency is less than the value set in
b2-01
[DC Injection/Zero SpeedThreshold] or E1-09 [Minimum Output Frequency]
.
Set this parameter to 0.00 to disable the function.
Note:
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...