YASKAWA
SIEPC71061753A GA500 Technical Manual
537
Item
Heavy Duty Rating (HD)
Normal Duty Rating (ND)
Application
A high overload tolerance is necessary during start up, acceleration,
deceleration, and equivalent conditions.
•
Extruder
•
Conveyor
•
Cranes and hoists
•
Constant torque or high overload capacity are necessary.
Overload tolerance is not necessary.
•
Fan
•
Pump
•
Blower
Overload Tolerance
150% - 60 seconds
110% - 60 seconds
Stall Prevent Level during Accel
150%
120%
Stall Prevent Level during Run
150%
120%
Carrier Frequency
2 kHz
2 kHz Swing-PWM
Note:
•
Set the stall prevention level during acceleration with
L3-02
and the stall prevention level during run with
L3-06
.
•
Changing
C6-01
also changes the maximum capacity of applicable drive motors. The drive automatically changes the setting values
E2-xx
and
E4-xx
to applicable values. The drive also automatically changes these parameters that depend on motor output:
–
b8-04 [Energy Saving Coefficient Value]
–
L2-03 [Minimum Baseblock Time]
–
L3-24 [Motor Accel Time @ Rated Torque]
–
n5-02 [Motor Inertia Acceleration Time]
■
C6-02: Carrier Frequency Selection
No.
(Hex.)
Name
Description
Default
(Range)
C6-02
(0224)
Carrier Frequency Selection
Sets the carrier frequency for the transistors in the drive.
Determined by A1-02, C6-
01, and o2-04
(Determined by A1-02)
Changes to the switching frequency will decrease audible noise and decrease leakage current.
Note:
Increasing the carrier frequency to more than the default setting will automatically decrease the drive current rating.
1 : 2.0 kHz
2 : 5.0 kHz (4.0 kHz for AOLV/PM)
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7 : Swing PWM1 (Audible Sound 1)
8 : Swing PWM2 (Audible Sound 2)
9 : Swing PWM3 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
B : Leakage Current Rejection PWM
Set this when the wiring distance between the drive and motor is long and there is a fault in the current monitor or
the drive detects and alarm because of the effect of a leakage current.
The carrier frequency is equivalent to 2.0 kHz.
F : User Defined (C6-03 to C6-05)
Use
C6-03 to C6-05
to set detailed setting values.
Note:
•
The carrier frequency for Swing PWM 1 is equivalent to 2.0 kHz. Swing PWM applies a special PWM pattern to decrease the audible
noise.
•
The setting range changes when the
A1-02 [Control Method Selection]
value changes:
–
5, 8 [OLV/PM, EZOLV]
: You cannot set to
7 to A
.
–
6 [AOLV/PM]
: You cannot set to
7 to A or F
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...