n8-63: Output Voltage Limit P Gain
No.
(Hex.)
Name
Description
Default
(Range)
n8-63
(057E)
Expert
Output Voltage Limit P
Gain
Sets the proportional gain for output voltage control. Usually it is not necessary to change this
setting.
1.00
(0.00 - 100.00)
■
n8-65: Speed Fdbk Gain @ oV Suppression
No.
(Hex.)
Name
Description
Default
(Range)
n8-65
(065C)
Expert
Speed Fdbk Gain @ oV
Suppression
Sets the gain of internal speed feedback detection suppression while the overvoltage suppression
function is operating as a magnification value. Usually it is not necessary to change this
parameter.
1.50
(0.00 - 10.00)
Adjust this parameter in these conditions:
•
If there is resonance or hunting when you use the overvoltage suppression function, increase the setting value.
•
If motor response is low when you use the overvoltage suppression function, decrease the setting value in 0.05-
unit increments.
■
n8-69: Speed Observer Control P Gain
No.
(Hex.)
Name
Description
Default
(Range)
n8-69
(065D)
Expert
Speed Observer Control P
Gain
Usually it is not necessary to change this setting. Sets the Proportional gain that the drive uses for
speed estimation.
1.00
(0.00 - 20.00)
■
n8-72: Speed Estimation Method Select
No.
(Hex.)
Name
Description
Default
(Range)
n8-72
(0655)
Expert
Speed Estimation Method
Select
Selects the speed estimation method. Usually it is not necessary to change this setting.
1
(0, 1)
0 : Method 1
1 : Method 2
■
n8-74: Light Load Iq Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-74
(05C3)
Expert
Light Load Iq Level
Set
n8-48 [Pull-in/Light Load Id Current]
to the percentage of load current (q-axis current) that
you will apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
30%
(0 - 255%)
Note:
•
If
n8-74
>
n8-75 [Medium Load Iq Level (low)]
, the drive will detect
oPE08 [Parameter Selection Error]
.
•
The change is linear between
n8-74
and
n8-75
and the level of the pull-in current from
n8-48
to
n8-78 [Medium Load Id Current]
.
■
n8-75: Medium Load Iq Level (low)
No.
(Hex.)
Name
Description
Default
(Range)
n8-75
(05C4)
Expert
Medium Load Iq Level
(low)
Set
n8-78 [Medium Load Id Current]
to the percentage of load current (q-axis current) that you
will apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
50%
(0 - 255%)
Note:
•
If
n8-74 [Light Load Iq Level]
>
n8-75
, the drive will detect
oPE08 [Parameter Selection Error]
.
•
The change is linear between
n8-74
and
n8-75
and the level of the pull-in current from
n8-48
to
n8-78 [Medium Load Id Current]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...