![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 506](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765506.webp)
506
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
b5-07: PID Offset Adjustment
No.
(Hex.)
Name
Description
Default
(Range)
b5-07
(01AB)
RUN
PID Offset Adjustment
Sets the offset for the PID control output as a percentage of the Maximum Output Frequency.
0.0%
(-100.0 - +100.0%)
■
b5-08: PID Primary Delay Time Constant
No.
(Hex.)
Name
Description
Default
(Range)
b5-08
(01AC)
RUN
Expert
PID Primary Delay Time
Constant
Sets the primary delay time constant for the PID control output. Usually it is not necessary to
change this setting.
0.00 s
(0.00 - 10.00 s)
Prevents resonance if there is a large quantity of mechanical friction or if rigidity is unsatisfactory. Set the value
larger than the resonant frequency cycle. A value that is too large will decrease drive responsiveness.
■
b5-09: PID Output Level Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-09
(01AD)
PID Output Level Selection
Sets the polarity of the PID output.
0
(0, 1)
Use this parameter in applications that decrease the drive output frequency when you increase the PID setpoint.
0 : Normal Output (Direct Acting)
A positive PID input increases the PID output (direct acting).
1 : Reverse Output (Reverse Acting)
A positive PID input decreases the PID output (reverse acting).
■
b5-10: PID Output Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
b5-10
(01AE)
RUN
PID Output Gain Setting
Sets the amount of gain to apply to the PID output.
1.00
(0.00 - 25.00)
Applies a gain to the PID output and can help when
b5-01 = 3 or 4 [PID Mode Setting = Fref + PID Trim, Fref +
PID Trim (D on feedback)]
.
■
b5-11: PID Output Reverse Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-11
(01AF)
PID Output Reverse
Selection
Sets the function that enables and disables reverse motor rotation for negative PID control output.
0
(0, 1)
This parameter is disabled when
b5-01 = 3, 4 [PID Mode Setting = Fref + PID Trim, Fref + PID Trim (D on
feedback)]
. There is no limit for PID output (PID output can be positive or negative). Operates the same as setting
“
1: Enabled: Negative lower limit
”
.
0 : Lower Limit is Zero
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative Output Accepted
When the PID output is negative, the motor will rotate in reverse. When
b1-04 = 1 [Reverse Operation Selection
= Reverse Disabled]
, the lower limit is 0.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...