12.11 o: Keypad-Related Settings
742
YASKAWA
SIEPC71061753A GA500 Technical Manual
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
◆
o4: Maintenance Mon Settings
o4 parameters
set the expected service life to help you know when to replace parts. The drive will show an alarm
to tell you when the replacement part interval is near.
■
o4-01: Elapsed Operating Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
When you select
o4-01
on the keypad, it will show the current value of
U4-01
in units of 10 hours (h). When you
change the setting of
o4-01
through the monitor, the
U4-01
count starts again as specified by the setting of
o4-01
.
Note:
Set this parameter in 10-hour (h) units. When
o4-01 = 30
,
U4-01 [Cumulative Ope Time] = 300 h
.
■
o4-02: Elapsed Operating Time Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
0
(0, 1)
0 : U4-01 Shows Total Power-up Time
Counts the time from when the drive is energized to when it is de-energized.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
■
o4-03: Fan Operation Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-03
(050E)
Fan Operation Time Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour
units.
0 h
(0 - 9999 h)
Use monitor
U4-03 [Cooling Fan Ope Time]
to view the total operation time of the cooling fan. When you
replace a cooling fan, set
o4-03 = 0
to reset
U4-03
. Select
o4-03
on the keypad to show the current value of
U4-03
in 10-hour (h) units. If you use the monitor to change
o4-03
, the recount of
U4-03
starts with the
o4-03
setting.
Note:
The drive sets
o4-03
in 10-hour (h) units. When
o4-03 = 30
,
U4-03 [Cooling Fan Ope Time]
will show
“
300 h
”
.
■
o4-05: Capacitor Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the
U4-05 [CapacitorMaintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-05 = 0
to reset
U4-05
. When the
o4-05
setting changes, the count of
U4-05
starts again as specified by the setting of
o4-05
. After you complete the configuration,
o4-05
automatically resets
to
0
.
Note:
The maintenance period changes for different operating environments.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...