12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
605
Figure 12.66 Baseblock Command Time Chart
ON : Baseblock (drive output stop)
OFF : Normal operation
■
9: Baseblock Command (N.C.)
Setting Value
Function
Description
9
Baseblock Command
(N.C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
The keypad flashes
bb [Baseblock]
. If you cancel the baseblock command when the Run command is active, the
drive will restart the motor and use the speed search function.
ON : Normal operation
OFF : Baseblock (drive output stop)
WARNING!
Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
■
A: Accel/Decel Ramp Hold
Setting Value
Function
Description
A
Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and
d4-01 = 1 [Freq Reference Retention
Select = Enabled]
, the drive will store the output frequency in memory. While the acceleration/deceleration ramp
hold command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to
“
d4-01: Freq Reference Retention Select
”
for more information.
■
B: Overheat Alarm (oH2)
Setting Value
Function
Description
B
Overheat Alarm (oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input terminal is ON. The alarm does not have an
effect on drive operation.
■
C: Analog Terminal Enable Selection
Setting Value
Function
Description
C
Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in
H3-14 [Analog Input Terminal Enable Sel]
.
ON : Terminal selected with
H3-14
is enabled
OFF : Terminal selected with
H3-14
is disabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...