SIEPC71061753A GA500 Technical Manual
Setting Value
Function
Description
Ref.
3F
PID Setpoint Selection 2
Set this function and
H1-xx = 3E [PID Setpoint Selection 1]
at the same time. Sets the function to switch the PID
setpoint to
b5-58 to b5-60 [PID Setpoint 2 to 4]
.
40
Forward RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 41 [Reverse Run Command
(2-Wire Seq)]
at the same time.
ON : Forward Run
OFF : Run Stop
Note:
•
If you activate the Forward Run command terminal and the Reverse Run command terminal, the drive will
detect minor fault/alarm
EF [FWD/REV Run Command Input Error]
and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-
Wire Seq 2)]
.
41
Reverse RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 40 [Forward Run Command
(2-Wire Seq)]
at the same time.
ON : Reverse Run
OFF : Run Stop
Note:
•
If you activate the Forward Run command terminal and the Reverse Run command terminal, the drive will
detect minor fault/alarm
EF [FWD/REV Run Command Input Error]
and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-
Wire Seq 2)]
.
42
Run Command (2-Wire
Sequence 2)
Sets the Run command for 2-wire sequence 2. Set this function and
H1-xx = 43 [FWD/REV Command (2-Wire Seq
2)]
at the same time.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as
H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire
Seq)]
.
43
FWD/REV (2-Wire
Sequence 2)
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and
H1-xx = 42 [Run Command (2-
Wire Sequence 2)]
together.
ON : Reverse run
OFF : Forward run
Note:
This function will not operate at the same time as
H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire
Seq)]
.
44
Offset Frequency 1
Sets the function to add the offset frequency set in
d7-01 [Offset Frequency 1]
to the frequency reference when the
terminal activates.
45
Offset Frequency 2
Sets the function to add the offset frequency set in
d7-02 [Offset Frequency 2]
to the frequency reference when the
terminal activates.
46
Offset Frequency 3
Sets the function to add the offset frequency set in
d7-03 [Offset Frequency 3]
to the frequency reference when the
terminal activates.
47
Node Setup (CANopen)
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from
the host controller.
60
DC Injection Braking
Command
Sets the command to use DC Injection Braking to stop the motor.
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM
motor.
61
Speed Search from Fmax
Sets the function to start speed search using an external reference although
b3-01 = 0 [Speed Search Selection at
Start = Disabled]
.
Note:
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same
time.
62
Speed Search from Fref
Sets the function to use an external reference to start speed search although
b3-01 = 0 [Speed Search Selection at
Start = Disabled]
.
Note:
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same
time.
63
Field Weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in
d6-
01[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit]
when the input terminal is activated.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...