![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 318](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765318.webp)
10.5 Model Specifications (Three-Phase 400 V Class)
318
YASKAWA
SIEPC71061753A GA500 Technical Manual
Model
Duty Rating
4018
4023
4031
4038
4044
4060
Output
Rated Output
Capacity
(kVA)
HD
11.3
13.7
18.3
23.6
29.7
34.3
ND
13.3
17.8
23.6
29
33.5
45.7
Rated Output
Current (A)
HD
14.8
18.0
24.0
31.0
39.0
45.0
ND
17.5
23.4
31.0
38.0
44.0
60
Overload Tolerance
•
HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10
minutes.
•
ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10
minutes.
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
•
V/f, OLV, OLV/PM: 590 Hz
•
AOLV/PM: 270 Hz
•
EZOLV: 120 Hz
Measures for
Harmonics
DC reactor
External options
Braking Device
Braking Transistor
Standard internal characteristics
EMC Filter
EMC Filter
IEC61800-3
Factory option
Models 4xxxE: Category C2 (Conducted emission)
Power Supply
Rated Voltage/Rated Frequency
Three-phase AC power supply 380 V to 480 V at 50/60 Hz
Permitted Voltage Fluctuation
-15% to +10%
Permitted Frequency Fluctuation
±5%
Input Power
(kVA)
HD
14
18
27
36
47
55
ND
18
22
35
40
55
74
*1
The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2
The rated output capacity is calculated with a rated output voltage of 440 V.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...