![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 600](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765600.webp)
12.8 H: Terminal Function Selection
600
YASKAWA
SIEPC71061753A GA500 Technical Manual
Setting Value
Function
Reference
67
Communications Test Mode
68
High Slip Braking (HSB)
6A
Drive Enable
75
Up 2 Command
76
Down 2 Command
77
ASR Gain (C5-03) Select
7A
KEB Ride-Thru 2 Activate (N.C.)
7B
KEB Ride-Thru 2 Activate (N.O.)
7C
Short Circuit Braking (N.O.)
Setting Value
Function
Reference
7D
Short Circuit Braking (N.C.)
7E
Reverse Rotation Identifier
7F
PID Bi-Directional Enable
90 to 96
DWEZ Digital Inputs 1 to 7
9F
DWEZ Disable
101 to 19F
Inverse Input of 1 to 9F
Sets the function of the selected MFDI to operate
inversely. To select the function for inverse input,
enter two digits 01 to 9F for the
“
xx
”
in
”
1xx
”
.
*1
Inverse input is not available.
*2
You cannot use
H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]
to set this.
■
H1-01: Terminal S1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H1-01
(0438)
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1.
40
(1 - 1FF)
Note:
The default setting is
F
when the drive is initialized for
3-Wire Initialization [A1-03 = 3330]
.
■
H1-02: Terminal S2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H1-02
(0439)
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2.
41
(1 - 1FF)
Note:
The default setting is
F
when the drive is initialized for
3-Wire Initialization [A1-03 = 3330]
.
■
H1-03: Terminal S3 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H1-03
(0400)
Terminal S3 Function
Selection
Sets the function for MFDI terminal S3.
24
(0 - 1FF)
■
H1-04: Terminal S4 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H1-04
(0401)
Terminal S4 Function
Selection
Sets the function for MFDI terminal S4.
14
(0 - 1FF)
■
H1-05: Terminal S5 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H1-05
(0402)
Terminal S5 Function
Selection
Sets the function for MFDI terminal S5.
3
(0 - 1FF)
Note:
When you initialize the drive for
3-Wire Initialization [A1-03 = 3330]
, the default setting is
0
.
■
H1-06: Terminal S6 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H1-06
(0403)
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6.
4
(0 - 1FF)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...