12.2 A: Initialization Parameters
472
YASKAWA
SIEPC71061753A GA500 Technical Manual
Note:
•
When decreased operation times are necessary for the application, for example with cranes and hoists, do not use S-curve characteristic
times.
•
The default setting for
C2-04 [S-Curve Time @ End of Decel]
will be 0.00 seconds. The default setting for other S-curve characteristics
will be 0.20 seconds. Set the acceleration/deceleration times and S-curve characteristic time correctly for acceleration/deceleration start
up and end. The recommended setting of the S-curve characteristics time is 0.2 to 1.0 seconds.
•
When you use the
C1-11 [Accel/Decel Time Switchover Freq]
, you can switch the acceleration/deceleration rate automatically during
acceleration/deceleration. The default setting is disabled.
When the
Output Frequency ≥ C1-11
, operate at the acceleration and deceleration times set in
C1-01
and
C1-02
When the
Output Frequency < C1-11
, operate at the acceleration and deceleration times set in
C1-07
and
C1-08
•
During low speed operation, if the
Output Frequency < E1-09 [Minimum Output Frequency]
in the S-Curve Time @ Start of Decel,
the drive will cancel the S-curve characteristics and do DC Inject Braking at Stop.
Dwell Function at Start
Adjustment Parameter
Name
b6-01
Dwell Reference at Start
b6-02
Dwell Time at Start
H2-xx = 5
Frequency Detection 2
Figure 12.5 Dwell Function at Start
Note:
•
If the mechanical operation of the holding brake is slow, use the Dwell Function at Start to prevent brake grinding (friction). Accelerate
after the brake is fully open.
•
When you use V/f Control or Open Loop Vector Control, set
b6-01 [Dwell Reference at Start] > Frequency Detection 2 (brake open
frequency)
.
•
If the motor torque is not sufficient during start up, use the DC Inject Braking function to secure the motor current (torque) before you
start the motor.
–
b2-02 [DC Injection Braking Current]
recommended setting: 50% to 75% (V/f Control, Open Loop Vector Control)
–
b2-03 [DC Inject Braking Time at Start]
recommended setting: 0.2 s to 0.5 s
DC Injection Braking at Stop Function
Note:
If you disconnect a drive from a motor when it is controlling the motor or during DC Injection Braking (Zero speed level), a voltage
surge can trigger a drive fault. When you use an electromagnetic contactor between the drive and motor, set
L8-07 = 1 or 2 [Output
Phase Loss Protection Sel = Fault when One Phase is Lost, Fault when Two Phases are Lost]
. If it necessary to disconnect the motor
and drive when you stop the elevator, fully close the holding brake and disconnect the drive while the Baseblock signal is ON. This does
not apply for emergency conditions.
Adjustment Parameter
Name
b2-01
DC Injection/Zero SpeedThreshold
b2-02
DC Injection Braking Current
b2-04
DC Inject Braking Time at Stop
H2-xx = 5
Frequency Detection 2
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...