7.10 Troubleshooting Without Fault Display
286
YASKAWA
SIEPC71061753A GA500 Technical Manual
◆
PID Output Fault
Causes
Possible Solutions
There is no PID feedback input.
•
Examine the MFAI terminal settings.
•
Make sure that
H3-02, H3-10 = B [MFAI Function Select = PID Feedback]
.
•
Make sure that the MFAI terminal settings agree with the signal inputs.
•
Examine the connection of the feedback signal.
•
Make sure that
b5-xx [PID Control]
is set correctly.
Note:
If there is no PID feedback input to the terminal, the detected value is 0, which causes a PID
fault and also causes the drive to operate at maximum frequency.
The detection level and the target value do not agree.
Use
H3-03, H3-11 [Terminal A1 and A2 Gain Setting]
to adjust PID target and feedback signal
scaling.
Note:
PID control keeps the difference between the target value and detection value at 0. Set the
input level for the values relative to each other.
Reverse drive output frequency and speed detection. When output frequency
increases, the sensor detects a speed decrease.
Set
b5-09 = 1 [PID Output Level Selection = Reverse output (reverse acting)]
.
◆
The Starting Torque Is Not Sufficient
Causes
Possible Solutions
Auto-Tuning has not been done in vector control method.
Do Auto-Tuning.
The control method was changed after doing Auto-Tuning.
Do Auto-Tuning again.
Stationary Auto-Tuning for Line-to-Line Resistance was done.
Do Rotational Auto-Tuning.
◆
The Motor Rotates after the Drive Output Is Shut Off
Causes
Possible Solutions
DC Injection Braking is too low and the drive cannot decelerate correctly.
•
Increase the value set in
b2-02 [DC Injection Braking Current]
.
•
Increase the value set in
b2-04 [DC Inject Braking Time at Stop]
.
The stopping method makes the drive coast to stop.
Set
b1-03 = 0 or 2 [Stopping Method Selection = Ramp to Stop, DC Injection Braking to Stop]
.
◆
The Output Frequency Is Lower Than the Frequency Reference
Causes
Possible Solutions
The frequency reference is in the Jump frequency range.
Adjust
d3-01 to d3-03 [Jump Frequency 1 to 3]
and
d3-04 [Jump Frequency Width]
.
Note:
Enabling the Jump frequency prevents the drive from outputting the frequencies specified in
the Jump range.
The upper limit for the frequency reference has been exceeded.
Set
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
to the
best values for the application.
Note:
This calculation supplies the upper value for the output frequency:
E1-04
×
d2-01
/ 100
A large load triggered Stall Prevention function during acceleration.
•
Decrease the load.
•
Adjust
L3-02 [Stall Prevent Level during Accel]
.
L3-01 = 3 [Stall Prevent Select duringAccel = ILim Mode]
has been set.
1.
Check whether the V/f pattern and motor parameter settings are appropriate, and set them
correctly.
2.
If this does not solve the problem, and it is not necessary to limit the current level of stall
during acceleration, adjust
L3-02
.
3.
If this does not solve the problem, set
L3-01 = 1 [Enabled]
.
The motor is rotating at this speed:
b2-01 [DC Injection/Zero SpeedThreshold]
≤ Motor Speed <
E1-09
[Minimum Output Frequency]
Set
E1-09 < b2-01
.
◆
The Motor Is Making an Audible Noise
Causes
Possible Solutions
100% of the rated output current of the drive was exceeded while operating
at low speeds.
If the sound is coming from the motor, set
L8-38 = 0 [Carrier Frequency Reduction = Disabled]
.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...