6.3 MEMOBUS/Modbus Communications
210
YASKAWA
SIEPC71061753A GA500 Technical Manual
Figure 6.4 Wiring Diagram for More than One Drive
Note:
1. Set DIP switch S2 to the ON position on the last drive of the MEMOBUS/Modbus communication network to enable the termination
resistor.
2. When you remove the shield from the ground terminal, it can make the communication quality better.
◆
MEMOBUS/Modbus Drive Operations
Drive parameters will apply to the settings when the drive is running during MEMOBUS/Modbus
communications. This section gives information about the available functions and their related parameters.
■
Executable Functions
A PLC can do these operations with MEMOBUS/Modbus communications. Parameter settings (except
H5-xx
) do
not have an effect on the availability of these operations.
•
Monitor the drive status and operate the drive
•
Set and view parameters
•
Fault Reset Procedure
•
Multi-function input settings
The input command from MEMOBUS/Modbus communications and MFDI terminals (S1 to S7) are linked by a
logical OR operation.
■
Drive Control
Select the external command that sets the frequency references and motor run/stop with MEMOBUS/Modbus
communications. Use the information in
to set the parameters as specified by the application.
Table 6.3 Necessary Parameter Settings for Drive Control from MEMOBUS/Modbus
LOCAL Control Selected
No.
Name
Setting Value
External reference 1
b1-01
Frequency Reference Selection 1
2 [Memobus/Modbus Communications]
b1-02
Run Command Selection 1
2 [Memobus/Modbus Communications]
External reference 2
b1-15
Frequency Reference Selection 2
2 [Memobus/Modbus Communications]
b1-16
Run Command Selection 2
2 [Memobus/Modbus Communications]
For more information about operation mode selection, refer to
[Frequency Reference Selection 1]
and
b1-02 [Run
Command Selection 1]
. Refer to H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection] for more
information about external command.
◆
Communications Timing
To prevent overrun of the slave side, the master cannot send a message to the same drive for a selected length of
time.
To prevent overrun of the master side, the slave cannot send a response message to the master for a selected length
of time.
This section gives information about message timing.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...