![YASKAWA CIPR-GA50C series Скачать руководство пользователя страница 639](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765639.webp)
12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
639
Note:
Refer to
“
PID Feedback Loss Detection
”
for more information.
■
3F: PID Feedback High
Setting Value
Function
Description
3F
PID Feedback High
The terminal activates when the drive detects
FbH [Excessive PID Feedback]
.
The drive detects
FbH [Excessive PID Feedback]
when the PID feedback value >
b5-36 [PID High Feedback
Detection Lvl]
for longer than the time set in
b5-37 [PID High Feedback Detection Time]
.
Note:
Refer to
“
PID Feedback Loss Detection
”
for more information.
■
4A: During KEB Ride-Thru
Setting Value
Function
Description
4A
During KEB Ride-Thru
The activates during KEB Ride-Thru.
Note:
Refer to
“
KEB Ride-Thru function
”
for more information.
■
4B: During Short Circuit Braking
Setting Value
Function
Description
4B
During Short Circuit
Braking
The terminal activates during Short Circuit Braking.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available when you use a PM motor.
•
Refer to "b2: DC Injection Braking and Short Circuit Braking" for more information.
■
4C: During Fast Stop
Setting Value
Function
Description
4C
During Fast Stop
The terminal activates when the fast stop is in operation.
■
4D: oH Pre-Alarm Reduction Limit
Setting Value
Function
Description
4D
oH Pre-Alarm Time Limit
The terminal activates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and
oH [Heatsink
Overheat]
does not clear after the drive decreases the frequency for 10 cycles.
Note:
Refer to
“
L8-03: Overheat Pre-Alarm Selection
”
for more information.
■
4E: Braking Transistor Fault (rr)
Setting Value
Function
Description
4E
Braking Transistor Fault
(rr)
The terminal activates when the internal braking transistor overheats and the drive detects an
rr [Dynamic Braking Transistor
Fault]
fault.
■
4F: Braking Resistor Overheat (rH)
Setting Value
Function
Description
4F
Braking Resistor Overheat
(rH)
The terminal activates when the braking resistor overheats and the drive detects an
rH [Braking Resistor Overheat]
fault.
The braking resistor overheats when the deceleration time is short and there is too much motor regeneration
energy.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...