12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
625
■
H2-26: Comparator 2 Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the
x-xx
part of the
Ux-xx [Monitor]
. For example,
set
H2-26 = 103
to monitor
U1-03 [Output Current]
.
103
(000 - 999)
Note:
•
The configurable monitor changes when the control method changes.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can set the terminal output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
•
For information on the comparator function, refer to
and
■
H2-27: Comparator 2 Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-27
(1547)
Comparator 2 Lower Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name
Description
Default
(Range)
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the
monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to
and
■
H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to
and
■
H2-31: Comparator 2 Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to
and
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...