12.6
E: Motor Parameters
E parameters
cover drive input voltage, V/f pattern, and motor parameters.
◆
E1: V/f Pattern for Motor 1
E1 parameters
are used to set the drive input voltage and motor V/f characteristics. To switch drive operation
from one motor to another motor, set the V/f characteristics for motor 1.
■
V/f Pattern Settings
The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference.
This product has been preconfigured with 15 voltage/frequency (V/f) patterns. Use
E1-03 [V/f Pattern Selection]
to select the V/f pattern that is appropriate for the application.
Additionally, one custom V/f pattern is available. Set
E1-03 = F [Custom]
and then manually set parameters
E1-
04 to E1-10
.
Table 12.45 Predefined V/f Patterns
Setting
Value
Specification
Characteristic
Application
0
VT, 50Hz
Constant torque
For general purpose applications. This pattern is used when the load torque is constant without
any rotation speed such as that used for linear conveyor systems.
1
VT, 60 Hz
2
Const Trq, 50Hz base, 60Hz max
3
Const Trq, 60 Hz base, 72 Hz max
4
VT, 50 Hz, 65% Vmid reduction
Derated Torque
Characteristics
This pattern is used for torque loads proportional to 2 or 3 times the rotation speed, such as is
the case with fans and pumps.
5
VT, 50 Hz, 50% Vmid reduction
6
VT, 60 Hz, 65% Vmid reduction
7
VT, 60 Hz, 50% Vmid reduction
8
High Trq, 50 Hz, 25% Vmin Boost
High starting torque
This pattern is used when strong torque is required during startup.
9
High Trq, 50 Hz, 65% Vmin Boost
A
High Trq, 60 Hz, 25% Vmin Boost
B
High Trq, 60 Hz, 65% Vmin Boost
C
Const Trq, 60 Hz base, 90 Hz max
Constant output
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when
operating at greater than 60 Hz.
D
Const Trq, 60 Hz base, 120 Hz max
E
Const Trq, 60 Hz base, 180 Hz max
F
V/f Pattern Selection
Constant torque
Enables a custom V/f pattern by changing
E1-04 to E1-13 [V/f Pattern for Motor 1]
. The
default settings for
E1-04 to E1-13
are the same as
Setting Value 1 [Const Trq, 60Hz base,
60Hz max]
.
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...