Overvoltage Suppression Function
Decreases the regenerative torque limit and increases the output frequency when the DC bus voltage increases to
prevent
ov
. This function can drive loads with cyclic regenerative operation, for example punch presses or other
applications with repeated crank movements. When you use this function, set
L3-11 = 1 [Overvoltage Suppression
Select = Enabled]
.
The drive adjusts the regenerative torque limit and the output frequency during overvoltage suppression to make
sure that the DC bus voltage is not more than the level set in
L3-17 [DC Bus Regulation Level]
.
Set these parameters as necessary when you use the overvoltage suppression function:
•
L3-20 [DC Bus Voltage Adjustment Gain]
•
L3-21 [OVSuppression Accel/Decel P Gain]
•
L3-24 [Motor Accel Time @ Rated Torque]
•
L3-25 [Load Inertia Ratio]
Note:
•
When overvoltage suppression is triggered, the motor speed is more than the frequency reference. Do not use overvoltage suppression
for applications where the frequency reference and the motor speed must align.
•
When you use a braking resistor, set
L3-11 = 0 [Disabled]
.
•
The overvoltage suppression function is enabled only when you operate immediately below the maximum frequency. Overvoltage
suppression does not increase the output frequency to more than the maximum frequency. Make sure that the motor and machine
specifications are correct for the application, then increase the maximum frequency.
•
If there is a sudden increase to a regenerative load,
ov
can occur.
■
L3-01: Stall Prevention during Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-01
(048F)
Stall Prevention during
Accel
Sets the method of the Stall Prevention During Acceleration.
1
(0 - 3)
Note:
When
A1-02 = 5 [Control Method Selection = OLV/PM]
, the setting range is
0 and 1
.
Stall prevention during acceleration prevents the stalling and stopping of motors when
oC [Overcurrent]
,
oL2
[Drive Overloaded]
, or
oL1 [Motor Overload]
is detected in cases of significant loads applied during acceleration
or sudden acceleration times regarding load inertia are set.
0 : Disabled
The Stall Prevention function does not operate during acceleration, and acceleration occurs for the set acceleration
time. If the acceleration time is too short, the motor will not fully accelerate during the set time, which causes the
drive to detect
oL1
or
oL2
and the motor to stop.
1 : Enabled
Enables the Stall Prevention During Acceleration function. Operation is different for different control methods.
•
V/f Control, Open Loop Vector Control, or EZ Open Loop Vector Control
When the output current is more than the value set in
L3-02 [Stall Prevent Level during Accel]
, the drive stops
acceleration. Deceleration is stopped once the output current falls below the value set in
L3-02
- 15%. The Stall
Prevention function level automatically falls for constant output ranges.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...