386
YASKAWA
SIEPC71061753A GA500 Technical Manual
11.11 L: Protection Functions
◆
L1: Motor Protection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
0 : No
1 : Variable Torque
2 : Constant Torque 10:1 Speed Range
3 : Constant Torque 100:1 SpeedRange
4 : PM Variable Torque
5 : PM Constant Torque
6 : Variable Torque (50Hz)
Note:
When only one motor is connected to a drive, set
L1-01 = 1 to 6 [Enabled]
.
External thermal relays are not necessary in these conditions.
Determined by A1-02
(0 - 6)
L1-02
(0481)
Motor Overload
Protection Time
Sets the operation time for the electronic thermal protector of the drive to prevent
damage to the motor. Usually it is not necessary to change this setting.
1.0 min
(0.1 - 5.0 min)
L1-03
(0482)
Motor Thermistor oH
Alarm Select
Sets drive operation when the PTC input signal entered into the drive is at the
oH3
[Motor Overheat Alarm]
detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop
3 : Alarm Only
3
(0 - 3)
L1-04
(0483)
Motor Thermistor oH
Fault Select
Sets the drive operation when the PTC input signal to the drive is at the
oH4 [Motor
Overheat Fault (PTC Input)]
detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop
1
(0 - 2)
L1-05
(0484)
Motor Thermistor Filter
Time
Sets the primary delay time constant for the PTC input signal entered to the drive. This
parameter prevents accidental motor overheat faults.
0.20 s
(0.00 - 10.00 s)
L1-08
(1103)
oL1 Current Level
Sets the reference current for the motor 1 thermal overload detection. When the current
level > 0.0 A, you cannot set this value < 10% of drive rated current.
0.0 A
(0.0 A or 10% to 150%
of the drive rated
current)
L1-09
(1104)
oL1 Current Level for
Motor 2
Sets the reference current for the motor 2 thermal overload detection. When the current
level > 0.0 A, you cannot set this value < 10% of drive rated current.
0.0 A
(0.0 A or 10 to150% of
the drive rated current)
L1-13
(046D)
Motor Overload Memory
Selection
Sets the function that keeps the current electronic thermal protector value when the
drive stops receiving power.
0 : Disabled
1 : Enabled
1
(0, 1)
L1-22
(0768)
RUN
Leakage Current Filter
Time1
Sets the leakage current detection reduction filter time constant during constant speed
run.
Note:
You can set this parameter when
C6-02 = B [Carrier Frequency Selection =
Leakage Current Detection Reduction Rate PWM]
.
Determined by C6-02
(0.0 - 60.0 s)
L1-23
(0769)
RUN
Leakage Current Filter
Time2
Sets the leakage current detection reduction filter time constant during acceleration/
deceleration.
Note:
•
You can set this parameter when
C6-02 = B [Carrier Frequency Selection =
Leakage Current Detection Reduction Rate PWM]
.
•
When the setting value increases, the current monitor also starts up slowly.
Examine the relevant sequence for problems.
Determined by C6-02
(0.0 - 60.0 s)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание CIPR-GA50C series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 157: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 157...
Страница 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 159: ...Standards Compliance 5 5 2 European Standards YASKAWA SIEPC71061753A GA500 Technical Manual 159...
Страница 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...
Страница 454: ...11 22 Parameters Changed by PM Motor Code Selection 454 YASKAWA SIEPC71061753A GA500 Technical Manual...