DC Pulse Power Supply
【
DC-10-4P
】
5
HOW TO OPERATE
60
5-2. How to operate in USER mode
This section describes how to operate in the USER mode.
In the USER mode, connecting the power supply with external control devices, such as a PLC, to
exchange necessary information from USER IO PORT.
*For the oscillating frequency, inversion pulse width, number of M/S connected units or the like, the setting is made from
the front face panel or the SERIAL communication.
5-2-1. Precautions for wiring of USER IO PORT
For wiring of USER IO PORT, you are recommended to follow the procedure below since noise may be
caused.
(1) Use of a twisted shield pair wire
(2) Insulation of signals by photocouplers etc. on the side of external connection devices
(3) Signal wires shall be arranged without tying with a power line.
(4) Connection in the shortest distance
Signal level
●
Digital signal
Digital signal input (DI):
15V/24V
2mA or mroe
Digital signal output (DO)
15V/24V
5mA
~
10mA/1ch
●
Analog signal
Analog signal input (AI)
0
~
+10V
Analog signal output (AO)
5mA or more
Table 5-5: Scale of analog signal output (AO)
DC-10-4P
Analog signal output range
Voltage
0
~
1500V
0V
~
10V
Current
0
~
25A
※
0V
~
10V
Power
0
~
10kW
※
0V
~
10V
* This depends on "the value of a single unit" × "the number of units."