DC Pulse Power Supply
【
DC-10-4P
】
5
HOW TO OPERATE
57
5-1-5. Parameter list
The changeable parameter list is shown below.
Table 5-2: System parameter
No
Description
Hierarchically
Setting rage
Variable
width
Unit
Initial value
1
Select operation mode
CNFG/SYTM/CONT
LOCAL/USER/HOST
―
―
USER
2
Select output control mode
CNFG/SYTM/MODE/SEL
POWER/VOLTAGE/
CURRENT
―
―
*
3
Make the settings so that
the output control mode
can be selected only on
the front panel.
CNFG/SYTM/MODE/LOCK
NO/YES
―
―
NO
4
Setting for number of units
of DC-10-4P connected.
CNFG/SYTM/UNIT
0
~
6
1
―
1*
5
Select whether or not to
use
the
terminating
resistance in use of
RS485.
CNFG/OTHR/HOST/TERM
NO/YES
―
―
NO
6
Network address setting
CNFG/OTHR/HOST/ADRS
1
~
127
1
―
1
7
SERIAL communication
rate
CNFG/OTHR/HOST/BPS
9600/19200/
38400/57600/115200
―
―
9600
8
Setting of optical
synchronization
PULS/OSC
CINT/CMST/CSLV
―
―
CINT
9
Setting of number of units
for optical synchronization
PULS/LINK
0 to 12 (system No.)
0 to 12
(number of systems)
1
―
0
0
*Follow the USER IO