DC Pulse Power Supply
【
DC-10-4P
】
4
DESCRIPTION OF FUNCTIONS
27
4-2-2-1. Pin allocation of USER IO PORT
The pin allocation in the USER control mode is as follows. For the USER control, connect to external
control devices including a PLC in reference to
"Table 5-6: USER control signal connecting
equivalent circuit."
Table 4-5: Pin allocation of USER IO PORT
Pin No.
Signal name
Type
Voltage
level
Return
Detail
1
COMA
Analog signal common
2
VOUT
AO
0-10V
COMA
Output voltage monitor signal*1
3
IOUT
Output current monitor signal*2
4
POUT
Output power monitor signal*2
5
COMA
Analog signal common
6
RESERVE
Not to be used.
Leave this open.
7
8
DC OFF
DI
0-15V
COMD
DC is not output at HIGH level.
The DC becomes unable to output only at LOW level. *4
9
RESERVE
Not to be used.
10
DC ON
DI
0-15V
COMD
DC is output at LOW level.
DC OFF signal is not output when the signal is HIGH.
11
READY
DO
0-15V/24V
COMD
Output at Low level when the output operation is possible. (Low level
even during the operation)
12
OUTPUT
Output at Low level during the output operation.
13
SETPOINT
The DC unit outputs at Low level during the output following the set
value.
14
FAIL
Output at Low level when an error is detected.
15
PULSE
PARAM
SEL
DI *6
0-15V
COMD
Switch signal for pulse parameters.
Select A for HIGH, and B for LOW.
16
HARC
DO
0-15V/24V
COMD
LOW level when the HARC is detected. *5
17
RESERVE
Not to be used. Leave this open.
18
19
COMD
Digital signal common
20
COML
LEVEL signal common
21
LEVEL
AI
0-10V
COMA
Power output set voltage (0 to 10V)*3
22
COMA
Analog signal common
23
24
RESERVE
Not to be used. Leave this open.
25
COMD
Digital signal common
26
RESET
DI *6
0-15V
COMD
Error reset (input at Low level)*4
27
PREG
Change of operation mode in combination, constant power, constant
current, and constant voltage.
Refer to 4-3-2.
28
IREG
29
RESERVE
Not to be used. Leave this open.
30
DC MODE
DI *6
0-15V
COMD
Change of oscillation mode by combination
Refer to 4-3-3 Continuous mode, One-pulse mode, and DC mode.
31
ONE PULSE
MODE
32
ACT
DO
0-15V/24V
COMD
LOW level when the pulse is in operation.
33
RESERVE
Not to be used. Leave this open.
34
COMD
Digital signal common
35
REMOTE
DO
0-15V/24V
COMD Output at Low level with the USER mode selected.
36
RESERVE
Not to be used. Leave this open.
37
INTERLOCK
DI *6
0-15V
COMD The interlock is released at Low level.
*1
The voltage is 0 to 1,500V against a signal voltage output level of 0 to 10V of the output voltage monitor.
*2
It varies depending on the number of power supplies. * (See Table 4-7 of 4-4)
*3
In the P-control:
the system power is provided corresponding to an output set voltage level of 0 to 10V*. (See Table 4-8 of 4-4)
In the I-control:
the system current is provided corresponding to an output set voltage level of 0 to 10V*. (See Table 4-8 of 4-4)
In the V-control:
0 to 1,500V is provided corresponding to an output set voltage level of 0 to 10V.
*4
*5
*6
Effective only in the USER mode.Error reset is possible from both OFF and RESET. Input should be 200msec or more (high level input when using
OFF, low level input when using RESET). In LOCAL mode, it is necessary to reset by operating the front panel.
Low level signal is output for the set cutoff time. (Example: Since the initial value is 0.2ms, a low level is output for 0.2ms)
DI is pulled up at 15V, but 24V etc. can be used externally. For details, refer to [Table 5-6: USER control signal connecting equivalent circuit] and
[Fig. 5-2: Recommended digital I/O connection circuit].