DC Pulse Power Supply
【
DC-10-4P
】
5
HOW TO OPERATE
53
SETP
:
this enables one to change the judgment criterion of SETPOINT.
The settable range is 2 to 8% in steps of 1%.
HOST
:
this enables one to change the settings in the SERIAL communication mode.
BPS:
SERIAL communication rate can be selected.
TERM: this enables one to select whether or not to use the terminating resistance in use of
RS485.
ADRS: this allows you to select the network address.
BPS: SERIAL communication rate can be selected.
Select 9600/19200/38400/57600/115200 bps.
TERM
:
this enables one to select whether or not to use the terminating resistance in use of
RS485.
NO: select this when you do not use the terminating resistance.
YES: select this when you use the terminating resistance.
ADRS
:
this allows you to set the network address.
The selectable range is 1 to 127 in steps of 1.
MONI
:
this allows you to confirm the number of times that HARD ARC is detected, and the
occurrence log of warnings and errors.
WARN: This displays the log of warnings.
FAIL: the error log is displayed.
BUS:
This displays the current input bus voltage (*).
ARC:
the number of times that HARD ARC is detected is displayed.
* Bus voltage: a voltage after three-phase AC rectification
WARN
:
This displays the log of warnings.
The latest warning log is displayed. Display the past warnings using the ▲ button.
The warning code, time after the breaker is closed, warning occurrence status (ON or
OFF), warning occurrence number, and warning name are displayed from the left.
FAIL
:
the error log is displayed.
The latest error log is displayed. Display the past error using the ▲ button.
The error code, time after the breaker is closed, warning occurrence status (ON or OFF), error
occurrence number, and error name are displayed from the left.