Error Signaling Module (ESM)
12.2.3 Forcing an Error Condition
The error response generation mechanism is testable by software by forcing an error condition. This
allows testing the ERROR pin functionality. By writing a dedicated key to the ESM Error Key Register
(ESMEKR), the ERROR pin is set to low for the specified time. The following steps describe how to force
an error condition:
1. Check ERROR Pin Status Register (ESMEPSR). This register must be 1 to switch into the error forcing
mode.
The ESM module cannot be switched into the error forcing mode if a failure has already been detected
in functional mode. The application command to switch to error forcing mode is ignored.
2. Write 5h to the ESM Error Key Register (ESMEKR). After that, the ERROR pin should output low (error
force mode).
Once the application puts the ESM module in the error forcing mode, the ERROR pin cannot indicate
the normal error functionality. If a failure occurs during this time, it gets still latched and the LTC is
reset and stopped. The error output pin is already driven low on account of the error forcing mode.
When the ESM is forced back to normal functional mode, the LTC becomes active and forces the
ERROR pin low until the expiration of the LTC (see
).
3. Write 0 to the ESM Error Key Register (ESMEKR) back to the active normal mode.
If there are no errors detected while the ESM module is in the error forcing mode, the ERROR pin
goes high immediately after exiting the error forcing mode.
Figure 12-9. ERROR Pin Timing - Example 7