Installing HiPath 3000
P31003-H3560-S403-54-7620, 09/05
4-112
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
inst_h3.fm
Installing HiPath 3750, HiPath 3700
Grounding the Main Distribution Frame
Mount and ground the MDF in accordance with the manufacturer’s instructions.
Figure 4-63
HiPath 3750 - Grounding connector for Basic Cabinet (for U.S. only)
HiPath 3750
Located in the electrical service
panel providing power to the Hi-
Path 3750 system.
Main grounding ter-
minal
Connection cable
with plug
Recommended: 12 AWG solid or stranded copper wire con-
ductor not exceeding 126 feet in length; blank or green/yel-
low.
Grounding point (example: Master
ground busbar)
AC outlet
Fuse box facil-
ity
20 A
120 VAC, 60 Hz
Neutral ground
Note: Single-point ground (SPG) configuration shown.
7
DANGER
This wire installation must be completed by a qualified electrician and must
comply with the national and local electrical codes.