inst_h3.fm
P31003-H3560-S403-54-7620, 09/05
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
4-5
Installing HiPath 3000
Installing HiPath 3800
4.2.3
Installing HiPath 3800 (Standalone)
This section contains information on how to install the HiPath 3800 communication system.
This chapter describes the standard installation procedures for the basic system. Refer to
Chapter 9 for information about supplementary equipment or expansions.
4.2.3.1
Selecting the Installation Site
Selecting a site
The customer usually has a preferred installation site in mind.
Make sure that the customer’s site meets the following guidelines:
●
To guarantee sufficient system ventilation, allow a minimum of 50 mm clearance between
the base of the cabinet and the ground and between stacked cabinets.
●
When cabinets are stacked, the basic cabinet must always be at the bottom of the stack.
●
Allow a minimum clearance of 10 cm both at the rear and the front of the cabinets for main-
taining boards and for wiring.
●
Do not expose the systems to direct sources of heat (for example sunlight and heaters).
●
Do not expose the systems to extremely dusty environments.
●
Avoid contact with chemicals.
●
Take every precaution to prevent the formation of condensation on the system during op-
eration. Systems covered with condensation must be dried before being used.
●
Observe the environmental conditions specified in Section 2.11.
For U.S. Only:
●
Install secondary-protection equipment.
●
Avoid standard carpeting, as it tends to produce electrostatic charges.
●
Ensure the availability of a power source that meets the requirements described in
Section 4.2.3.1.1.
●
Ensure that Siemens equipment is 40 in. (101.6 cm) from other electrical equipment. The
National Electrical Code (NEC) requires 36 in. (91.44 cm) of clearance in front of electrical
equipment and 40 in. (101.6 cm) of clearance from other electrical service equipment.
Information on the design of the HiPath 3800 can be found in Section 2.2.2.1.
Содержание HiPath 3000 V3.0 or later Gigaset M1 Professional
Страница 1: ...HiPath 3000 V6 0 HiPath 5000 V6 0 Provisional Service Manual ESHB 60 004 05 09 22 09 05 ...
Страница 1168: ...Figures P31003 H3560 S403 54 7620 09 05 W 12 HiPath 3000 V6 0 HiPath 5000 V6 0 Provisional Service Manual hp3hp5shLOF fm ...
Страница 1178: ...Tables P31003 H3560 S403 54 7620 09 05 X 10 HiPath 3000 V6 0 HiPath 5000 V6 0 Provisional Service Manual hp3hp5shLOT fm ...
Страница 1201: ......