Installing HiPath 3000
P31003-H3560-S403-54-7620, 09/05
4-68
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
inst_h3.fm
Installing HiPath 3800
4.2.7.1.1
Mounting the Main Distribution Frame (MDFU-E)
The MDFU-E main distribution frame should be installed in the direct vicinity of the system
(note length of connection cable) and at eye level.
The packing material contains a drawing that can be used as a drilling template.
Procedure for wall mounting
4.2.7.1.2
Laying the Line Network and Jumpers on the MDFU-E
Jumpers, external line network
Most main distribution frames do not have an external side. You must jumper them to the in-
coming line network (see jumpering duct, Figure 4-37). Use a standard wiring tool for laying the
cable wires.
Surge protector
To divert surges caused by lightning, insert surge protectors on
●
lines that leave the system buildings (outside stations)
●
lines > 500 m long.
Connect the polarized surge protectors to the plugging locations on the splitting strip described
above (see Figure 4-39).
Step
Activity
1.
Use the template to drill the holes.
2.
Insert the wall anchors and screw in the screws, leaving 5 mm projecting.
3.
Remove the housing cover and mount the MDFU-E on the brackets.
4.
Tighten the screws through the holes.
7
Danger
Be sure to connect the main protective earthing terminal on all system cabinets and
all main distribution frames to the grounding point of the electrical building installa-
tion before connecting up the peripherals (for example, potential equalization bus).
Содержание HiPath 3000 V3.0 or later Gigaset M1 Professional
Страница 1: ...HiPath 3000 V6 0 HiPath 5000 V6 0 Provisional Service Manual ESHB 60 004 05 09 22 09 05 ...
Страница 1168: ...Figures P31003 H3560 S403 54 7620 09 05 W 12 HiPath 3000 V6 0 HiPath 5000 V6 0 Provisional Service Manual hp3hp5shLOF fm ...
Страница 1178: ...Tables P31003 H3560 S403 54 7620 09 05 X 10 HiPath 3000 V6 0 HiPath 5000 V6 0 Provisional Service Manual hp3hp5shLOT fm ...
Страница 1201: ......